Skip to main content
❄️ HVAC Engineering

HVAC Duct Sizing Calculator

Calculate equivalent duct diameters and cross-sectional areas based on CFM airflow requirements.

Round & Rectangular
Airflow (CFM)
Constant Velocity

HVAC sizing — Quick answer

An HVAC calculator estimates the cooling / heating capacity (BTU/h or kW) needed to condition a space, based on floor area, climate, insulation, and internal heat gains.

Rule-of-thumb: BTU/h = floor area × 25 (mild) to 60 (hot/sunny)
Manual J approach: Q = U × A × ΔT + solar + occupant + equipment gains

Worked example: 200 sq ft bedroom, mild climate, average insulation. BTU/h = 200 × 25 = 5,000 BTU/h (0.5 ton, 1.5 kW). Hot sunny upper-floor room: 200 × 50 = 10,000 BTU/h.

HVAC sizing rule of thumb by climate and room type

Room areaMild (BTU/h)Moderate (BTU/h)Hot/sunny (BTU/h)Tons
100 sq ft2,5003,5006,0000.25–0.5
200 sq ft5,0007,00012,0000.5–1.0
400 sq ft10,00014,00024,0001.0–2.0
800 sq ft20,00028,00048,0002.0–4.0
1,500 sq ft37,50052,50090,0003.0–7.5
2,500 sq ft62,50087,500150,0005.0–12.0

Standard / source: ACCA Manual J (residential load calc); ASHRAE 90.1 (energy efficiency); ISO 13790 (thermal performance).

Used for: AC unit selection, mini-split sizing, ductless heat-pump capacity, commercial RTU sizing, HVAC contractor quotes.

🌬️ HVAC Duct Sizing Calculator

Duct cross-section and equivalent round diameter from airflow and target air velocity, with a rectangular-duct suggestion.

Duct Area (mm²)
Round Diameter (mm)
Rect Width (mm)
Velocity (m/s)

⚠️ A=Q/v. Typical velocities: supply 4–8 m/s, return 3–5 m/s, low-noise <4 m/s. Confirm with friction-loss method for long runs.

HVAC Equation for Duct Sizing

The relationship between Volume of air (CFM), the cross sectional Area of the duct (sq. ft), and the Velocity of the air (FPM) is defined by the basic continuity equation.

Airflow (Q)
Q (CFM) = A (sq. ft.) × V (FPM)
Round Equivalent Diameter (inches)
D = √[ (A × 144) / (π / 4) ]

Frequently Asked Questions

How do you calculate CFM for a duct?

CFM is calculated by multiplying the internal Cross Sectional Area of the duct (in square feet) by the Air Velocity (in Feet Per Minute).

What is the formula for HVAC cooling load?

Total cooling load (kW) = Sensible load + Latent load. Sensible load covers heat from: solar radiation through glass, heat conduction through walls/roofs, people (75W sensible each), lighting (watts × 3.41 BTU/hr), equipment, and ventilation air. Latent load covers moisture from occupants (55W/person) and ventilation. ASHRAE Handbook of Fundamentals and Manual J provide detailed calculation methods.

What is the difference between BTU and kW in HVAC?

BTU (British Thermal Unit) measures heat energy; BTU/hr measures cooling/heating power. Conversion: 1 kW = 3,412 BTU/hr. A 5kW air conditioner equals ~17,060 BTU/hr. In the US, residential HVAC is rated in BTU/hr (range: 5,000–60,000 BTU/hr). Commercial systems are rated in tons of refrigeration: 1 ton = 12,000 BTU/hr = 3.517 kW.

How do I calculate the right air conditioner size?

A simplified rule of thumb: allow 150–200 BTU/hr (44–59W) per m² of floor area in a typical climate. For a 20m² room: 20 × 175 = 3,500W = 3.5 kW. However, accurate sizing requires Manual J or ASHRAE load calculations accounting for climate zone, insulation levels, window area and orientation, occupancy, and local solar intensity. Oversizing causes short-cycling and poor dehumidification.

What is COP and SEER in HVAC equipment?

COP (Coefficient of Performance) = useful heating or cooling output (kW) / electrical power input (kW). A COP of 3.5 means 3.5 kW of cooling for each 1 kW of electricity. SEER (Seasonal Energy Efficiency Ratio) = total seasonal cooling output (BTU) / total seasonal electrical input (Wh) — it accounts for varying conditions through the season. Minimum SEER ratings in the US are now 14–15 depending on climate region.

What is sensible vs latent heat in air conditioning?

Sensible heat changes air temperature (measured by thermometer) — caused by solar gain, conduction, equipment, and lighting. Latent heat changes air moisture content (humidity) without changing temperature — caused by people perspiring, cooking, and humid outdoor air. In tropical climates, latent load can be 40–60% of total cooling load. Most packaged air conditioners handle both; in high-humidity climates, dedicated dehumidification or dedicated outdoor air systems (DOAS) may be needed.

Ready to perform complete calculations?

Use the full AI Calculator to get precise results with thousands of options and export a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 350+ engineering calculators · PDF report export