Electrical Engineering Calculator
45+ precision electrical calculators — Ohm's Law, Power Factor Correction, Voltage Drop, Cable Sizing, Ampacity, Tray & Trunking Fill, Conduit Fill, Short Circuit Analysis & more. Verified against IEC, BS EN & NEC standards.
Popular Electrical Calculators
📖 See also: Cable Sizing Guide · Engineering Formulas · Best Engineering Calculator
🔌 Cable Sizing Calculator Library
12 cable sizing tools — covering IEC 60364-5-52, NEC NFPA 70 Article 310, BS 7671:2018+A2 and AS/NZS 3008.1.1; copper and aluminium conductors; installation methods A1, B1, C, D1, E; single-phase and three-phase circuits. Each variant pre-loads realistic defaults and a worked example.
By standard
By conductor material
By installation method
By circuit type
About Our Electrical Engineering Calculators
The electrical category is the largest on AI Calculator and the one most heavily relied on by working engineers. It covers the standards-driven design math behind cable sizing, voltage drop, short-circuit current, transformer sizing, motor starting, conduit fill, power-factor correction, and the everyday electronics calculations of resistor colour codes, LED current limiting, op-amp gain, and 555-timer frequencies. Every standards-driven calculator (cable sizing, voltage drop, short circuit) implements the equations directly from the relevant code — IEC 60364 and IEC 60909 for international/IEC practice, NEC NFPA 70 for North America, BS 7671 for the UK, and AS/NZS 3008 for Australia and New Zealand. Each page shows which standard it follows and what assumptions (ambient temperature, installation method, grouping factor) drive the answer.
Headline Calculators in This Electrical Suite
- Cable Sizing Calculator — the master tool. Pick the standard (IEC 60364 / NEC / BS 7671 / AS-NZS 3008), the conductor (Cu / Al), the installation method (A1 through F), and the calculator returns the minimum cross-sectional area that satisfies current-carrying capacity, voltage-drop, and short-circuit thermal limits.
- Voltage Drop Calculator — %VD from cable resistance, reactance, current, and length. NEC recommends < 3% for branch and 5% combined; IEC/BS practice is typically < 4% from supply.
- Short Circuit Calculator (IEC 60909) — symmetrical and peak fault current at any node, used for switchgear breaking-capacity selection.
- 3-Phase Power Calculator — P, Q, S relationships; line-to-line vs line-to-neutral voltage; balanced and unbalanced loading.
- Ohm’s Law Calculator — V = IR, P = VI in all six rearrangements, including the power triangle.
- Transformer Sizing Calculator — kVA from connected load + diversity + future-load margin; primary/secondary current at design voltage.
- Motor Starting Current Calculator — locked-rotor current and voltage dip during DOL / star-delta / soft-start / VFD start of an induction motor.
- Conduit Fill Calculator — NEC 40% fill rule (or 31% / 53% per conductor count) for sizing EMT, RMC, PVC, and ENT conduit.
- Power Factor Calculator — capacitor kVAR required to correct from existing PF to a target PF.
Standards Implemented & Why It Matters
An electrical design that doesn’t cite a standard is a liability waiting to happen. The calculators here are explicit about which code they follow because the answers genuinely differ between codes. NEC permissible ampacity for a 50 mm² copper THWN-2 in EMT at 30 °C ambient is 175 A; the IEC 60364 ampacity for the same cross-section in installation method E (open in air) at the same ambient is 192 A; in method A1 (in conduit in thermally insulated wall) it drops to 119 A. These aren’t small differences, and the wrong standard can lead to either undersized cable (a fire risk) or over-engineered cost. The cable-sizing calculator therefore exposes the standard as a top-level input, not a hidden assumption.
A Typical Workflow: Sizing a Three-Phase Feeder
For a 75 kW, 415 V three-phase induction motor running at full load PF 0.85: full-load current = 75,000 / (√3 × 415 × 0.85) = 122.7 A. Apply NEC/IEC motor sizing (typically 125% of FLC for branch-circuit conductor): 122.7 × 1.25 = 153 A required ampacity. Run the cable-sizing calculator with ambient = 35 °C, installation method = on cable tray (typically C in IEC), correction factor for ambient = 0.93, and the calculator returns 70 mm² copper as the minimum. Voltage drop on a 50 m run = (√3 × 122.7 × 0.05 × 0.378) / 415 × 100 ≈ 0.67% — well within the 4% IEC limit. Short-circuit calc then confirms the cable’s 1-second I²t rating exceeds the upstream breaker’s let-through energy.
Frequently Asked Questions
Why does the cable-sizing answer change when I switch standard?
Because the underlying ampacity tables are different. NEC, IEC, BS, and AS/NZS each derive their tables from slightly different reference conditions (ambient, conductor temperature, insulation, installation grouping). The calculator picks the relevant table for the standard you select.
Are the short-circuit results good enough to size switchgear breaking capacity?
For three-phase faults at a single node — yes, the IEC 60909 calculation is standard. For more complex network studies (multiple sources, motor contribution, asymmetrical faults) you need a full power-systems analysis tool such as ETAP, PSS/E, or DIgSILENT.
Does the voltage-drop calculator account for harmonic distortion?
No — it uses fundamental-frequency resistance and reactance. For high-harmonic loads (VFDs, big rectifier banks), apply a derating factor or run a harmonic study; the answer here is the fundamental-frequency baseline.
What if my installation method isn’t in the standard list?
Pick the closest method and apply judgement. The standards documents themselves (NEC chapter 9, IEC 60364-5-52) describe each method in detail; if your installation is borderline between two methods, take the more conservative ampacity.
Related calculator categories: Mechanical engineering · Civil & structural · Chemical & process · Cable sizing guide · Engineering formulas reference