Skip to main content
⚡ Electrical Power

Motor Starting Current Calculator

Calculate starting inrush current and Locked Rotor Amps (LRA) for induction motors.

Inrush Current
Locked Rotor Amps
NEMA Code Letters

Motor starting current — Quick answer

Motor starting current (also called inrush or locked-rotor amps, LRA) is the surge current drawn when an induction motor energises before it spins up. Typically 5-8× the full-load current.

Istart = Kstart × IFLA
Where Kstart = 6 (DOL), 2 (star-delta), 2–3 (soft-start), 1–1.5 (VFD)

  • IFLA — motor full-load amps (nameplate)
  • Kstart — starting method multiplier
  • LRA — locked-rotor amps (~7× FLA for NEMA Design B)

Worked example: 22 kW three-phase 415 V motor, FLA = 40 A. Direct-on-line start: Istart = 6 × 40 = 240 A. Star-delta starter: 2 × 40 = 80 A. VFD: roughly 40–50 A (rated-current limited).

Motor starting current by method

Starting methodMultiplierTorqueUse case
Direct-on-line (DOL)6–8 × FLA100% ratedSmall motors < 7.5 kW
Star-delta (Y/Δ)2 × FLA33% ratedLight-load starts, fans, pumps
Auto-transformer1.5–4 × FLA50–80%Medium motors with reduced-torque start
Soft-starter2–3 × FLAAdjustableConveyors, mills, controlled ramp
VFD / inverter1.0–1.5 × FLAFull at any speedVariable-speed drives, modern installs

Standard / source: NEMA MG 1 (motor design classes); IEC 60034-12 (starting performance); NEC NFPA 70 Article 430 (motor branch circuits).

Used for: Switchgear breaking-capacity selection, transformer voltage-dip checks, generator sizing, cable sizing for motor branch circuits, soft-starter / VFD selection.

🔧 Motor Starting Current Calculator

Full-load current, locked-rotor (starting) current and starting kVA for an induction motor — by NEMA code letter or a locked-rotor multiple — across DOL, star-delta, autotransformer, soft-starter and VFD starting.

Full-Load Current
Locked-Rotor (DOL)
Starting Current
Starting kVA

⚠️ NEMA MG-1 code-letter kVA/HP bands; star-delta gives ~⅓ of DOL, autotransformer ~tap². Field LRC varies with motor design — confirm against the nameplate.

Motor Inrush Current Principles

When an AC induction motor is energized, it draws a significant surge of current, known as starting current or inrush current, before settling down to its normal run current (Full Load Amps).

Starting Current
I_start = FLA × Multiplier

The multiplier depends on the starting method:

  • Direct On Line (DOL): 500% to 800% of FLA
  • Star-Delta: Approx. 33% of DOL current (~200% FLA)
  • Soft Starter: 200% to 400% of FLA
  • VFD: 100% to 200% of FLA

Frequently Asked Questions

How many times is starting current compared to full load current?

For a Direct-On-Line (DOL) starter, the starting current is typically 6 times (or 600% of) the motor's Full Load Amps (FLA).

What is motor starting current?

Motor starting current (inrush or locked-rotor current) is the high current drawn the moment a motor starts, when the rotor is stationary. It typically equals 6–8× the motor's full-load current (FLC) for direct-on-line (DOL) starting. This surge typically lasts 2–10 seconds while the rotor accelerates to rated speed, then current drops to the normal running level.

Why does a motor draw so much current at startup?

At startup, the stationary rotor generates zero back-EMF (counter-electromotive force). Without back-EMF to oppose the supply voltage, the stator windings act as near-short-circuit load. As the rotor accelerates, back-EMF builds up and limits current to the normal operating value. The starting current is limited primarily by stator impedance, which is low at standstill.

What motor starting methods reduce inrush current?

Methods to reduce motor starting current: Star-Delta starter — reduces starting voltage to 1/√3, limiting starting current to ~33% of DOL (but starting torque also reduces to 33%); Autotransformer starter — selectable 50/65/80% voltage taps; Soft starter — electronic gradual voltage ramp, 2–4× FLC starting current; VFD (Variable Frequency Drive) — smoothest start, typically 1.5× FLC, highest cost and most flexible.

How does motor starting current affect transformer sizing?

When a motor starts, the inrush current (typically 600–800% FLC) causes a voltage dip at the transformer secondary proportional to: ΔV% ≈ (Istart × %Ztransformer) / Irated_transformer × 100. A large motor starting on a small transformer can cause a 10–20% voltage dip, tripping sensitive equipment. Rule of thumb: motor kW should not exceed 25–33% of transformer kVA for DOL starting.

What is a NEMA locked-rotor code letter?

NEMA assigns code letters (A–V) to motors indicating locked-rotor kVA per horsepower. Common codes: Code F — 5.0–5.6 kVA/hp; Code G — 5.6–6.3 kVA/hp; Code H — 6.3–7.1 kVA/hp; Code J — 7.1–8.0 kVA/hp; Code K — 8.0–9.0 kVA/hp. Higher letters mean higher starting current. Most standard NEMA squirrel-cage motors are Code G or H. The code letter is on the motor nameplate.