Skip to main content
⚡ Electrical Power

Power Factor Calculator

Calculate the required capacitor bank size (in kVAR) to improve power factor.

PF Correction
Required kVAR
Apparent Power

Power factor — Quick answer

Power factor (cos φ) is the ratio of real to apparent power in an AC circuit. Low PF wastes capacity in cables and transformers and triggers utility surcharges. Capacitor banks correct it.

PF = P (real, kW) / S (apparent, kVA) = cos φ
Qrequired = P × (tan φ1 − tan φ2)  kVAR

  • P — real power (kW)
  • S — apparent power (kVA)
  • Q — reactive power (kVAR) — positive = inductive, negative = capacitive
  • φ1, φ2 — phase angles before and after correction

Worked example: 100 kW load currently at PF 0.70, correct to 0.95. φ1 = acos(0.70) = 45.6°, tan = 1.020. φ2 = acos(0.95) = 18.2°, tan = 0.329. Qcap = 100 × (1.020 − 0.329) = 69.1 kVAR capacitor bank.

Capacitor kVAR required per kW to correct from existing PF to 0.95

Existing PFφ1tan φ1kVAR per kW (→ 0.95)
0.6053.1°1.3331.004
0.7045.6°1.0200.691
0.7541.4°0.8820.553
0.8036.9°0.7500.421
0.8531.8°0.6200.291
0.9025.8°0.4840.156
0.9223.1°0.4260.097

Standard / source: IEEE 1459 (power definitions); IEC 60871 (capacitor banks); local utility tariffs penalise PF < 0.90 typically.

Used for: Industrial PF correction, reducing utility demand charges, increasing transformer capacity, motor-load PF compensation.

⚙️ Power Factor Correction Calculator

Find the capacitor kVAR needed to improve power factor from existing to target, plus the resulting current reduction.

Capacitor kVAR
kVA Before
kVA After
Current Saved (A)

⚠️ Qc = P·(tanφ₁−tanφ₂). Capacitor in kVAR. Verify against utility tariff and harmonics before installing.

Power Factor Correction Equations

Power factor is the ratio of real power (kW) to apparent power (kVA). Correcting it requires installing capacitors that supply reactive power (kVAR), effectively reducing the total apparent power drawn from the grid.

Required Correction (Q_c) in kVAR
Q_c = P × [ tan(arccos(PF_i)) - tan(arccos(PF_t)) ]

Where:

  • P = Real power in kW
  • PF_i = Initial power factor
  • PF_t = Target power factor

Frequently Asked Questions

How do you calculate required kVAR for power factor correction?

The required capacitor bank size (kVAR) is calculated by taking the real power (kW) and multiplying it by the difference between the tangents of the initial and target power factor angles.

What is power factor and why does it matter?

Power factor (PF) = Real Power (kW) / Apparent Power (kVA) = cos φ. It ranges from 0 to 1.0. A PF of 0.8 means only 80% of electrical energy drawn from the grid is doing useful work; 20% is reactive power cycling back and forth. Low PF forces electrical infrastructure (cables, transformers, switchgear) to be oversized to handle the extra current — costing money even though no useful work is done.

What causes low power factor?

Low (lagging) power factor is caused by inductive loads that draw lagging reactive current: induction motors (especially when lightly loaded — PF can drop to 0.3–0.5 at no-load); transformers; fluorescent and HID lighting with magnetic ballasts; arc furnaces; and welding equipment. Most industrial facilities run at PF of 0.7–0.9 without correction.

How much capacitance do I need for power factor correction?

Required capacitor bank size: Qc (kVAR) = P × (tan φ1 − tan φ2). Where P is load in kW, φ1 is the current power factor angle (arccos of existing PF), φ2 is the target power factor angle (arccos of target PF). Example: 100 kW load at 0.75 PF, target 0.95 PF: Qc = 100 × (tan 41.4° − tan 18.2°) = 100 × (0.882 − 0.329) = 55.3 kVAR.

What are utility power factor penalties?

Most utilities impose penalty tariffs when PF drops below 0.85 or 0.90. Penalties typically add 1–3% to the bill per 0.01 below the threshold. For example, operating at 0.75 PF instead of 0.90 could add 15–45% to electricity costs. Beyond billing, low PF causes: overloaded cables and transformers, increased I²R losses, voltage sag, and reduced available capacity in distribution equipment.

What is the difference between displacement power factor and true power factor?

Displacement PF (DPF) = cos of the phase angle between fundamental voltage and current — the classic power factor measured by older instrumentation. True (total) PF also accounts for harmonic distortion: PF_true = DPF / √(1 + THD_I²). Variable speed drives (VFDs), UPS systems, and switch-mode power supplies generate significant current harmonics, making true PF lower than displacement PF. Modern power quality meters measure both.