What is Cable Sizing?
Cable sizing is the process of selecting the minimum conductor cross-section (in mm² for metric, or AWG for US) that safely carries the required current under the actual installation conditions — without overheating or causing an excessive voltage drop at the load.
Undersized cables are a leading cause of electrical fires. Oversized cables are safe but wasteful and expensive. The goal is to find the optimal minimum size that satisfies three criteria simultaneously:
- Current-carrying capacity — the cable's derated ampacity must exceed the design current
- Voltage drop — the drop along the cable run must not exceed 3–5% of supply voltage
- Short-circuit protection — the cable must withstand fault currents until the protective device disconnects
International Cable Sizing Standards
All international standards follow the same fundamental methodology: select a conductor whose tabulated current-carrying capacity (Iz), after applying applicable derating (correction) factors, remains at or above the design current (Ib).
How to Calculate Cable Size — Step by Step
- Step 1 — Determine Design Current (Ib) For single-phase loads: Ib = P / (V × PF). For three-phase: Ib = P / (√3 × VLL × PF × η). For motors, use the full-load current from the motor nameplate.
- Step 2 — Choose Installation Method (IEC Reference Method) Method A1/A2 (in conduit in wall), B1/B2 (in conduit on wall / trunking), C (clipped direct), D1 (direct buried), D2 (in duct in ground). The method determines which current-carrying capacity table to use.
- Step 3 — Apply Derating Factors Ca = temperature correction factor, Cg = grouping/bunching factor, Ci = insulation factor (thermal insulation). Combined factor = Ca × Cg × Ci.
-
Step 4 — Calculate Required Tabulated Current (It)
Select the cable size whose tabulated rating Iz ≥ It from the relevant standard table.Required tabulated currentIt = Ib ÷ (Ca × Cg × Ci)
-
Step 5 — Check Voltage Drop
Must not exceed 3% for lighting or 5% for power (IEC/BS 7671), or 3% for branch circuits (NEC).Voltage drop check (IEC/BS 7671)ΔU% = (Ib × L × mV/A/m) ÷ (1000 × Vn) × 100
- Step 6 — Verify Protection Coordination Confirm: In (protective device) ≤ Iz (derated cable ampacity). For short-circuit protection, check the cable's adiabatic limit: S ≥ √(I²t) / k.
IEC 60364-5-52 — Current-Carrying Capacity Reference Table
The values below are from IEC 60364-5-52 Table B.52.4 for copper conductors with XLPE/EPR insulation (90°C rated) at 30°C ambient, with no grouping. For PVC (70°C) cables, values are approximately 10–15% lower.
| Cross-Section (mm²) | Method A1 (A) | Method B1 (A) | Method C (A) | Method D1 (A) | AWG Approx. |
|---|---|---|---|---|---|
| 1.5 | 17.5 | 19.5 | 22 | 26 | 14 AWG |
| 2.5 | 24 | 27 | 30 | 34 | 12 AWG |
| 4 | 32 | 36 | 40 | 44 | 10 AWG |
| 6 | 41 | 46 | 51 | 56 | 8 AWG |
| 10 | 57 | 63 | 70 | 75 | 6 AWG |
| 16 | 76 | 85 | 94 | 97 | 4 AWG |
| 25 | 99 | 112 | 119 | 121 | 2 AWG |
| 35 | 121 | 138 | 147 | 143 | 1 AWG |
| 50 | 145 | 168 | 179 | 167 | 1/0 AWG |
| 70 | 183 | 213 | 229 | 203 | 2/0 AWG |
| 95 | 220 | 258 | 278 | 239 | 3/0 AWG |
| 120 | 253 | 299 | 322 | 271 | 4/0 AWG |
Source: IEC 60364-5-52:2009 Table B.52.4 — Copper conductors, XLPE insulation, 3-core cable, 30°C ambient. Actual values may vary by manufacturer.
Temperature Derating Factors (Ca)
When the ambient temperature differs from the standard 30°C reference, the cable's current-carrying capacity must be derated by the factor Ca from IEC 60364-5-52 Table B.52.14:
| Ambient Temp (°C) | Ca — PVC (70°C) | Ca — XLPE/EPR (90°C) |
|---|---|---|
| 25 | 1.06 | 1.04 |
| 30 (reference) | 1.00 | 1.00 |
| 35 | 0.94 | 0.96 |
| 40 | 0.87 | 0.91 |
| 45 | 0.79 | 0.87 |
| 50 | 0.71 | 0.82 |
| 55 | 0.61 | 0.76 |
| 60 | 0.50 | 0.71 |
Worked Example — Cable Sizing for a 15kW Motor
Given: 15kW, 400V three-phase motor, PF = 0.85, η = 0.92. Cable installed in conduit on wall (Method B1), ambient 40°C, 3 circuits in the same conduit.
Step 1 — Design Current
Step 2 — Derating Factors
Ca (40°C, XLPE) = 0.87 | Cg (3 circuits) = 0.73
Step 3 — Required Tabulated Current
Step 4 — Select Cable
From Method B1 table: 10mm² XLPE has Iz = 63A ≥ 43.6A ✅. The 6mm² (46A) also satisfies the requirement, so select 6mm² — no wait, 46A > 43.6A ✅ — 6mm² is the minimum cable size.
Step 5 — Voltage Drop Check (30m run)
Result: Select 6mm² copper XLPE 3-core cable. Verify the protective device (In ≤ 46A derated rating).
Frequently Asked Questions
Cable size is calculated in 4 steps: (1) Find design current Ib. (2) Apply derating factors for temperature (Ca) and grouping (Cg) to get required tabulated current It = Ib ÷ (Ca × Cg). (3) Select the cable from IEC 60364-5-52 whose ampacity Iz ≥ It. (4) Verify voltage drop stays below 3% (lighting) or 5% (power) per IEC/BS 7671. For 20A at 40°C with 3 cables grouped: It = 20 ÷ (0.87 × 0.73) = 31.5A → select 4mm² (36A in conduit).
For a 32A circuit clipped directly to a wall (IEC Method C) at 30°C with no other cables grouped alongside it: from IEC 60364-5-52 a 6mm² XLPE copper cable is rated 51A (Method C) — this safely handles 32A. If the cable is in conduit (Method B1), the 6mm² rated at 46A still works. Always also check voltage drop for long cable runs over 15–20m.
Per IEC 60364-5-52 and BS 7671:2018: maximum 3% for lighting circuits and 5% for power circuits (from the origin of the installation). Per NEC Article 210.19: 3% recommended for branch circuits, 5% total from service panel to outlet. For sensitive equipment (medical, data centres), keep voltage drop below 1–2%.
A derating (correction) factor reduces a cable's rated current to account for real installation conditions. Apply derating when: (1) Ambient temperature > 30°C — use Ca factor from IEC Table B.52.14. (2) Multiple cables are grouped or bunched together — use Cg factor from IEC Table B.52.17. (3) Cable passes through thermal insulation — use Ci factor. Always multiply all applicable factors together: combined factor = Ca × Cg × Ci.
The main differences are: (1) Conductor sizes — IEC uses mm² (1.5, 2.5, 4, 6, 10…), NEC uses AWG and kcmil. (2) Temperature ratings — IEC references 70°C (PVC) and 90°C (XLPE); NEC uses 60°C, 75°C and 90°C columns. (3) Voltage drop limits — IEC recommends 3%/5%; NEC recommends 3% for branch circuits. (4) Installation methods — IEC uses reference methods A1–D2; NEC uses conduit types (EMT, RMC, PVC). Both require derating for ambient temperature and conduit fill.