⚡ IEC 60364 · BS 7671 · NEC Article 310

Cable Sizing Calculator

Calculate the minimum conductor cross-section for any circuit. Apply temperature derating, grouping factors and voltage drop checks — verified against international standards.

IEC 60364-5-52
BS 7671:2018+A2
NEC Article 310
PDF Report Export
100% Free
⚡ Open Full Cable Sizing Calculator 📖 Read the Guide
203
Engineering Calculators
6
Disciplines
IEC
Verified Standard
PDF
Report Export

⚡ Quick Cable Size Estimator

Get an instant cable size estimate. For full calculations with derating, voltage drop and PDF export, use the complete calculator →

Required It (A)
Minimum Cable Size
Cable Ampacity Iz
Derating Applied

⚠️ This is an estimate only. Use the full calculator for precise results with voltage drop, protection coordination and PDF report.

What is Cable Sizing?

Cable sizing is the process of selecting the minimum conductor cross-section (in mm² for metric, or AWG for US) that safely carries the required current under the actual installation conditions — without overheating or causing an excessive voltage drop at the load.

Undersized cables are a leading cause of electrical fires. Oversized cables are safe but wasteful and expensive. The goal is to find the optimal minimum size that satisfies three criteria simultaneously:

  • Current-carrying capacity — the cable's derated ampacity must exceed the design current
  • Voltage drop — the drop along the cable run must not exceed 3–5% of supply voltage
  • Short-circuit protection — the cable must withstand fault currents until the protective device disconnects

International Cable Sizing Standards

IEC 60364-5-52Wiring Systems — International
BS 7671:2018+A2:2022IET Wiring Regulations — UK
NEC Article 310National Electrical Code — USA
AS/NZS 3000:2018Wiring Rules — Australia/NZ
HD 60364-5-52CENELEC — Europe

All international standards follow the same fundamental methodology: select a conductor whose tabulated current-carrying capacity (Iz), after applying applicable derating (correction) factors, remains at or above the design current (Ib).

How to Calculate Cable Size — Step by Step

  1. Step 1 — Determine Design Current (Ib) For single-phase loads: Ib = P / (V × PF). For three-phase: Ib = P / (√3 × VLL × PF × η). For motors, use the full-load current from the motor nameplate.
  2. Step 2 — Choose Installation Method (IEC Reference Method) Method A1/A2 (in conduit in wall), B1/B2 (in conduit on wall / trunking), C (clipped direct), D1 (direct buried), D2 (in duct in ground). The method determines which current-carrying capacity table to use.
  3. Step 3 — Apply Derating Factors Ca = temperature correction factor, Cg = grouping/bunching factor, Ci = insulation factor (thermal insulation). Combined factor = Ca × Cg × Ci.
  4. Step 4 — Calculate Required Tabulated Current (It)
    Required tabulated current
    It = Ib ÷ (Ca × Cg × Ci)
    Select the cable size whose tabulated rating Iz ≥ It from the relevant standard table.
  5. Step 5 — Check Voltage Drop
    Voltage drop check (IEC/BS 7671)
    ΔU% = (Ib × L × mV/A/m) ÷ (1000 × Vn) × 100
    Must not exceed 3% for lighting or 5% for power (IEC/BS 7671), or 3% for branch circuits (NEC).
  6. Step 6 — Verify Protection Coordination Confirm: In (protective device) ≤ Iz (derated cable ampacity). For short-circuit protection, check the cable's adiabatic limit: S ≥ √(I²t) / k.

IEC 60364-5-52 — Current-Carrying Capacity Reference Table

The values below are from IEC 60364-5-52 Table B.52.4 for copper conductors with XLPE/EPR insulation (90°C rated) at 30°C ambient, with no grouping. For PVC (70°C) cables, values are approximately 10–15% lower.

Cross-Section (mm²) Method A1 (A) Method B1 (A) Method C (A) Method D1 (A) AWG Approx.
1.5 17.5 19.5 22 26 14 AWG
2.5 24 27 30 34 12 AWG
4 32 36 40 44 10 AWG
6 41 46 51 56 8 AWG
10 57 63 70 75 6 AWG
16 76 85 94 97 4 AWG
25 99 112 119 121 2 AWG
35 121 138 147 143 1 AWG
50 145 168 179 167 1/0 AWG
70 183 213 229 203 2/0 AWG
95 220 258 278 239 3/0 AWG
120 253 299 322 271 4/0 AWG

Source: IEC 60364-5-52:2009 Table B.52.4 — Copper conductors, XLPE insulation, 3-core cable, 30°C ambient. Actual values may vary by manufacturer.

Temperature Derating Factors (Ca)

When the ambient temperature differs from the standard 30°C reference, the cable's current-carrying capacity must be derated by the factor Ca from IEC 60364-5-52 Table B.52.14:

Ambient Temp (°C) Ca — PVC (70°C) Ca — XLPE/EPR (90°C)
25 1.06 1.04
30 (reference) 1.00 1.00
35 0.94 0.96
40 0.87 0.91
45 0.79 0.87
50 0.71 0.82
55 0.61 0.76
60 0.50 0.71

Worked Example — Cable Sizing for a 15kW Motor

Given: 15kW, 400V three-phase motor, PF = 0.85, η = 0.92. Cable installed in conduit on wall (Method B1), ambient 40°C, 3 circuits in the same conduit.

Step 1 — Design Current

Ib = 15,000 ÷ (√3 × 400 × 0.85 × 0.92) = 27.7A

Step 2 — Derating Factors

Ca (40°C, XLPE) = 0.87  |  Cg (3 circuits) = 0.73

Step 3 — Required Tabulated Current

It = 27.7 ÷ (0.87 × 0.73) = 27.7 ÷ 0.635 = 43.6A

Step 4 — Select Cable

From Method B1 table: 10mm² XLPE has Iz = 63A ≥ 43.6A ✅. The 6mm² (46A) also satisfies the requirement, so select 6mm² — no wait, 46A > 43.6A ✅ — 6mm² is the minimum cable size.

Step 5 — Voltage Drop Check (30m run)

ΔU% = (27.7 × 30 × 7.3 mV/A/m) ÷ (1000 × 400) × 100 = 1.52% ✅ (< 5%)

Result: Select 6mm² copper XLPE 3-core cable. Verify the protective device (In ≤ 46A derated rating).

Frequently Asked Questions

How do I calculate cable size for a circuit?

Cable size is calculated in 4 steps: (1) Find design current Ib. (2) Apply derating factors for temperature (Ca) and grouping (Cg) to get required tabulated current It = Ib ÷ (Ca × Cg). (3) Select the cable from IEC 60364-5-52 whose ampacity Iz ≥ It. (4) Verify voltage drop stays below 3% (lighting) or 5% (power) per IEC/BS 7671. For 20A at 40°C with 3 cables grouped: It = 20 ÷ (0.87 × 0.73) = 31.5A → select 4mm² (36A in conduit).

What cable size do I need for a 32A circuit?

For a 32A circuit clipped directly to a wall (IEC Method C) at 30°C with no other cables grouped alongside it: from IEC 60364-5-52 a 6mm² XLPE copper cable is rated 51A (Method C) — this safely handles 32A. If the cable is in conduit (Method B1), the 6mm² rated at 46A still works. Always also check voltage drop for long cable runs over 15–20m.

What is the maximum voltage drop for a cable?

Per IEC 60364-5-52 and BS 7671:2018: maximum 3% for lighting circuits and 5% for power circuits (from the origin of the installation). Per NEC Article 210.19: 3% recommended for branch circuits, 5% total from service panel to outlet. For sensitive equipment (medical, data centres), keep voltage drop below 1–2%.

What is a derating factor and when do I apply it?

A derating (correction) factor reduces a cable's rated current to account for real installation conditions. Apply derating when: (1) Ambient temperature > 30°C — use Ca factor from IEC Table B.52.14. (2) Multiple cables are grouped or bunched together — use Cg factor from IEC Table B.52.17. (3) Cable passes through thermal insulation — use Ci factor. Always multiply all applicable factors together: combined factor = Ca × Cg × Ci.

What is the difference between IEC and NEC cable sizing?

The main differences are: (1) Conductor sizes — IEC uses mm² (1.5, 2.5, 4, 6, 10…), NEC uses AWG and kcmil. (2) Temperature ratings — IEC references 70°C (PVC) and 90°C (XLPE); NEC uses 60°C, 75°C and 90°C columns. (3) Voltage drop limits — IEC recommends 3%/5%; NEC recommends 3% for branch circuits. (4) Installation methods — IEC uses reference methods A1–D2; NEC uses conduit types (EMT, RMC, PVC). Both require derating for ambient temperature and conduit fill.

Ready to Size Your Cable?

Use the full AI Calculator to get precise results with all derating factors, voltage drop, short-circuit checks, and export a professional PDF report.

⚡ Open Full Cable Sizing Calculator — Free

No registration required · 203 engineering calculators · PDF report export