Skip to main content
NEC Article 220 · Verified

NEC Dwelling Load Calculator

Find the right circuit breaker or fuse for a load — applying the NEC 125% continuous-load rule and rounding to the next standard size in NEC 240.6.

125% rule
NEC 240.6 sizes
From A or W
Wire ampacity
100% Free
⚡ Open Full Electrical Calculator 📖 Read the Guide

In short — NEC dwelling load calculation

NEC Article 220 gives you two legal methods, and they can give different service sizes. You may use either.

Standard (220.42–220.60): apply a demand factor to each category, then add.

Optional (220.82): add all nameplate loads, take the first 10 kVA at 100% and the rest at 40%, then add HVAC separately.

  • 220.12 — general lighting = 3 VA per ft² of living space.
  • 220.52 — at least two 1,500 VA small-appliance circuits, plus 1,500 VA laundry.
  • 220.42 — demand factor: first 3,000 VA at 100%, 3,001–120,000 at 35%, remainder at 25%.
  • 220.55 Table, Column C — one household range ≤12 kW counts as 8,000 VA, not its nameplate.
  • 220.60 — heating and air conditioning are noncoincident. Take the larger. Never add them.

Worked example (NEC Annex D, D1(a)). 1,500 ft² dwelling, 12 kW range. Lighting 4,500 + small appliance 3,000 + laundry 1,500 = 9,000 VA. Demand: 3,000 + (6,000 × 0.35) = 5,100 VA. Range: 8,000 VA. Total 13,100 VA ÷ 240 V = 54.6 A → a 100 A service (230.79(C) minimum). This calculator reproduces that example exactly.

⚡ NEC Article 220 dwelling load calculation

Both methods, side by side, with every demand factor shown. Enter nameplate VA — the calculator applies the Code's factors.

Standard method — total
Standard — amps
Standard — service
Optional method — total
Optional — amps
Optional — service

⚠️ NEC-based. Verify against the current edition and have a licensed electrician or engineer review before installation.

Standards & method

✓ Formula independently verified 12 July 2026
Governing standard
NEC (NFPA 70) Article 220
Clauses applied
  • 220.12 — general lighting, 3 VA/ft²
  • 220.52 — small-appliance and laundry branch circuits
  • 220.42 — lighting demand factors (100% / 35% / 25%)
  • 220.53 — 75% demand for four or more fastened appliances
  • 220.54 — dryer, 5,000 VA minimum
  • Table 220.55 Column C — household range demand
  • 220.60 — noncoincident loads (larger of heat or cool)
  • 220.82 — optional method (10 kVA at 100%, remainder at 40%)
  • 230.79(C) — 100 A minimum service for a one-family dwelling
Verification
Reproduces NEC Annex D, Example D1(a) exactly: 1,500 ft² dwelling with a 12 kW range → 13,100 VA / 54.6 A. 15 numeric assertions, all passing.
Core formula
Standard method: Σ(general lighting × 220.42 demand) + appliances + Table 220.55 range demand + larger of heat/AC (220.60)
Why this matters
Heating and cooling are noncoincident (220.60) — take the LARGER, never the sum. And a 12 kW range is 8,000 VA per Table 220.55 Column C, not 12,000. Both errors inflate the service size.
Independently verified
12 July 2026 — every demand factor re-derived from the Code and checked against the NEC's own worked example.

Why this matters: The two most common errors are adding heating and cooling (220.60 says take the larger — they never run together), and using a range's nameplate rating instead of the Table 220.55 Column C demand (a 12 kW range counts as 8,000 VA, not 12,000).

Results are for guidance. Verify against the current edition of the NEC and have a licensed electrician or engineer review before installation.

How the two methods differ — and why the answer changes

Article 220 gives you a choice, and the choice has money in it. The optional method (220.82) usually gives a smaller service for a modern all-electric home, because it applies a single 40% factor to everything above 10 kVA rather than demanding each category separately.

The three mistakes that fail an inspection

  1. Adding heat and A/C together. 220.60 calls them noncoincident — you take the larger and ignore the smaller. They do not run at the same time, so the service never sees both. Adding them oversizes the service and costs the customer real money.
  2. Using the range nameplate. A 12 kW range does not count as 12,000 VA. Table 220.55 Column C says one range up to 12 kW is 8,000 VA. Above 12 kW you add 5% per kW.
  3. Forgetting the dryer floor. 220.54 sets a 5,000 VA minimum regardless of nameplate. A 4,000 VA dryer still counts as 5,000.

Which method should you use?

Whichever gives the smaller service — both are legal. The optional method is available for any dwelling served by a single 120/240 V or 208Y/120 V three-wire service of 100 A or more, which covers essentially every house. This calculator runs both and tells you which one wins.

NEC Dwelling Load Calculator — frequently asked

How do you calculate the electrical load for a house?

Use NEC Article 220. Take 3 VA per square foot of living space for general lighting, add at least two 1,500 VA small-appliance circuits and a 1,500 VA laundry circuit, then apply the 220.42 demand factor: the first 3,000 VA at 100% and the remainder at 35%. Add the range demand from Table 220.55 Column C, the dryer (5,000 VA minimum), fastened appliances, and the larger of heating or air conditioning. Divide the total by the service voltage to get amps.

Do you add heating and air conditioning together in a load calculation?

No. NEC 220.60 treats them as noncoincident loads — they cannot run at the same time, so you use the larger of the two and ignore the smaller. Adding them is one of the most common load-calculation errors and it oversizes the service.

How much VA is a 12 kW range in a load calculation?

8,000 VA, not 12,000. NEC Table 220.55 Column C gives the demand for household electric ranges: a single range rated 12 kW or less counts as 8,000 VA. Above 12 kW, Note 1 adds 5% to the Column C value for each kW above 12.

What is the minimum service size for a house?

NEC 230.79(C) requires a minimum of 100 A for a one-family dwelling, regardless of what the calculation gives. If your calculated load is 54.6 A, you still install a 100 A service.

What is the difference between the standard and optional load calculation methods?

The standard method (220.42–220.60) applies a separate demand factor to each category of load. The optional method (220.82) sums all nameplate loads, takes the first 10 kVA at 100% and everything above that at 40%, then adds HVAC separately. Both are legal; the optional method usually gives a smaller service for a modern all-electric home.

Is a 200 amp service enough for my house?

Run the calculation. A typical 2,000–2,500 ft² all-electric home with a range, dryer, water heater and central heat usually lands between 150 A and 200 A by the optional method. Adding an EV charger, a hot tub or a heat pump can push it past 200 A — which is why the calculation exists rather than a rule of thumb.

Does the floor area include the garage and basement?

NEC 220.12 measures the outside dimensions of the dwelling and includes areas adaptable to future use, but excludes open porches, garages, and unused or unfinished spaces not adaptable for future use. A finished basement counts; an unfinished crawl space does not.