Skip to main content
⚡ Protection & Distribution

Breaker Size Calculator

Find the right circuit breaker or fuse for a load — applying the NEC 125% continuous-load rule and rounding to the next standard size in NEC 240.6.

125% rule
NEC 240.6 sizes
From A or W
Wire ampacity
100% Free
⚡ Open Full Electrical Calculator 📖 Read the Guide

Breaker sizing — Quick answer

Size the breaker at 125% of a continuous load (100% for non-continuous), then round up to the next standard rating.

Required = Iload × 1.25 (continuous)  |  Breaker = next standard ≥ Required  |  Wire ampacity ≥ Breaker

Worked example: A 16 A continuous load → 16 × 1.25 = 20 A → 20 A breaker, wired with conductor rated ≥ 20 A. A 24 A continuous load → 30 A → 30 A breaker.

Standard breaker sizes (NEC 240.6)

15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A

Used for: branch-circuit and feeder protection, panel schedules, EV chargers, HVAC, appliance circuits.

⚡ Breaker & Fuse Size Calculator

Enter the load current, or enter power and voltage to compute it. Choose continuous if the load runs 3 hours or more.

Load current
Required (×factor)
Breaker / fuse
Min wire ampacity

⚠️ NEC 210.20/215.3: device ≥ 125% continuous + 100% non-continuous. Motors & HVAC follow special rules (NEC 430/440).

A circuit breaker or fuse protects the conductor from overload and short circuit. Its rating must be high enough to carry the load without nuisance tripping, but no higher than the wire can safely handle. The governing rule for ordinary loads is the 125% continuous-load factor: the device and conductor are rated for the non-continuous load at 100% plus the continuous load at 125%. After applying the factor you round up to the next standard size in NEC 240.6.

Reviewed: June 19, 2026 · Author: Naveen P N, Founder — AI Calculator · Verified against: NEC (NFPA 70) Articles 210.20, 215.3, 240.6.

Safety notice. Overcurrent protection is life-safety equipment. This tool covers general lighting and appliance branch circuits and feeders; motors (NEC 430), HVAC (NEC 440) and other special loads have their own rules. Final design must follow your local code and be verified by a licensed electrician. See our disclaimer.

How breaker sizing works

Three steps cover the vast majority of branch circuits:

Step 1 — required ampacity
Irequired = (continuous load × 1.25) + (non-continuous load × 1.0)
Step 2 — choose the device
Breaker = next standard rating ≥ Irequired  (NEC 240.6)
Step 3 — match the conductor
Conductor ampacity ≥ Breaker rating

A "continuous load" is one expected to run at its maximum for three hours or more — lighting, EV charging, fixed heating. The 25% margin prevents the breaker and the lugs from running hot during long, steady operation.

Worked example 1 — EV charger

Scenario: A 40 A continuous EV charging load on a 240 V circuit.

Required ampacity
40 A × 1.25 = 50 A

50 A is itself a standard size, so use a 50 A breaker with conductor rated at least 50 A (typically 6 AWG copper at 75 °C). This is exactly why a 40 A charger is installed on a 50 A circuit.

Worked example 2 — sizing from power

Scenario: A 3-phase, 415 V, 11 kW continuous heater at power factor 1.0.

Load current
I = P / (√3 × V × PF) = 11000 / (1.732 × 415 × 1) = 15.3 A
Required & device
15.3 × 1.25 = 19.1 A → next standard = 20 A breaker

Use the electrical power calculator to get the current, then size the cable with the cable-sizing calculator so its ampacity is at least 20 A.

Frequently Asked Questions

What size breaker do I need for my load?

Take the load current, multiply by 1.25 if it is continuous (3+ hours), then choose the next standard breaker at or above that. 16 A continuous → 20 A breaker. The conductor must be rated for at least the breaker size.

Why multiply continuous loads by 125%?

NEC 210.20(A) and 215.3 require the device and conductor to be rated for at least 125% of a continuous load. The 25% margin prevents overheating during long steady operation. Multiplying by 1.25 equals dividing by 0.8 (the 80% rule).

What are the standard breaker sizes?

NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A and up. Round up to the next standard size.

Can the breaker be larger than the wire rating?

No — the breaker protects the wire, so conductor ampacity must be at least the breaker rating (with limited exceptions like motor circuits and the small-conductor next-size-up rule). Size the cable to match the breaker.

How do I size a breaker from watts?

Convert power to current first: I = P ÷ V (DC/1-phase) or I = P ÷ (√3 × V × PF) (3-phase). Then apply the 125% continuous factor and round up to the next standard size.

Ready to perform complete calculations?

Use the full AI Calculator suite for cable sizing, fault current and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 350+ engineering calculators · PDF report export