⚡ NEC NFPA 70 · USA

NEC Cable Sizing Calculator

Calculate minimum wire size per NEC (NFPA 70) Article 310. Compute AWG / kcmil from load current, ambient temperature derating and conductor adjustment factors per Tables 310.16 and 310.15(B)(3)(a).

Standard-Verified
Worked Example
Free · No Login

In short — nec nfpa 70 cable / wire sizing

NEC NFPA 70 Cable / Wire Sizing selects the minimum standard cable cross-section whose corrected ampacity Iz exceeds the design current Ib. Per NEC Table 310.16 (75°C copper column):

It = Ib ÷ (Ca × Cg × Ci)   →   pick smallest cable where Iz ≥ It

Worked example: Ib = 30 A, Method C, ambient correction Ca = 0.87, no grouping  →  It = 30 ÷ (0.87 × 1.00) = 34.5 A → 4 mm² (Iz = 40 A ≥ 34.5 A). Selected cable: 4 mm² copper (≈ 10 AWG).

Standard: NEC Table 310.16 (75°C copper column).

Used for: USA / Canada / Mexico residential, commercial and industrial wiring; UL-listed conductor selection; AWG and kcmil sizing.

⚡ NEC Cable Sizing — Quick Estimator

Pre-loaded with defaults for Conductors run in raceway exposed to air. Edit any field to recompute.

Required It (A)
Minimum Cable Size
Cable Ampacity Iz
Derating Applied

⚠️ Estimate based on copper / XLPE conductors per IEC 60364-5-52 Table B.52.4. Use the full calculator for voltage drop, short-circuit and protection coordination.

NEC NFPA 70 Cable / Wire Sizing — Method

NEC Article 310 (NFPA 70) governs wire sizing in the United States, Canada (CSA-modified), Mexico (NOM) and many countries that adopted the US system. Wire is sized by reading Table 310.16 (75°C copper is most common), then derating for ambient temperature (Table 310.15(B)(2)(a)) and the number of current-carrying conductors in a single raceway (Table 310.15(B)(3)(a)). The 80 % continuous-load rule (Article 210.19/215.2) applies to feeders and branch circuits.

Required tabulated current
It = Ib ÷ (Ca × Cg × Ci)

Where:

  • Ib — design current of the circuit (A), from the load calculation
  • Ca — ambient temperature correction (1.00 at 30 °C reference)
  • Cg — grouping / bunching factor (1.00 for a single circuit)
  • Ci — thermal-insulation factor (1.00 if the cable is in free air; 0.50 if fully buried in insulation)

Then pick the smallest cable cross-section in NEC Table 310.16 (75°C copper column) whose tabulated ampacity Iz ≥ It.

Related cable sizing calculators

Other standard- and method-specific cable-sizing calculators in the same series — same procedure, different reference tables and defaults:

Frequently Asked Questions

Which NEC table do I use for wire ampacity?

NEC Table 310.16 is the standard for conductors in conduit or cable. Use the 60 °C column for #14–#10 AWG NM cable, the 75 °C column for typical THHN/THWN-2 in conduit, and the 90 °C column only when terminations are 90 °C-rated (most are 75 °C). For free-air conductors use Table 310.17 instead — values are ~1.5× higher.

How do I apply NEC ambient temperature correction?

Multiply the table ampacity by the temperature correction factor (TCF) from the bottom of Table 310.16. Examples for 75 °C conductors: TCF = 1.05 at 21–25 °C, 1.00 at 26–30 °C, 0.94 at 31–35 °C, 0.88 at 36–40 °C, 0.82 at 41–45 °C. Below freezing TCF can rise above 1.10 — useful in cold storage.

When does the NEC 80 % continuous-load rule apply?

NEC 210.19 (branch circuits) and 215.2 (feeders) require: conductor and overcurrent device shall be sized for 125 % of the continuous load + 100 % of non-continuous. Equivalently, the rated ampacity of the conductor must be ≥ continuous load ÷ 0.80. A continuous load is one expected to run ≥ 3 hours (lighting, HVAC, EV charging).

How does NEC handle conductor adjustment for raceway fill?

Table 310.15(B)(3)(a) reduces ampacity when 4–6 current-carrying conductors share a raceway (×0.80), 7–9 (×0.70), 10–20 (×0.50), 21–30 (×0.45). Neutral, ground and equipment-grounding conductors do not count unless they carry harmonic current — see 310.15(B)(5).

How do AWG sizes convert to mm² for international projects?

Approximate equivalents: 14 AWG ≈ 2.08 mm² (use 2.5 mm²), 12 AWG ≈ 3.31 mm² (use 4 mm²), 10 AWG ≈ 5.26 mm² (use 6 mm²), 8 AWG ≈ 8.37 mm² (use 10 mm²), 6 AWG ≈ 13.3 mm² (use 16 mm²), 4 AWG ≈ 21.2 mm² (use 25 mm²), 2 AWG ≈ 33.6 mm² (use 35 mm²), 1/0 AWG ≈ 53.5 mm² (use 50 mm²), 4/0 AWG ≈ 107 mm² (use 95 mm²), 250 kcmil ≈ 127 mm² (use 120 mm²).

Is NEC ampacity higher or lower than IEC 60364?

Generally similar within 10 %. NEC 75 °C copper Table 310.16 #12 AWG = 25 A vs IEC 4 mm² Method B1 = 36 A (XLPE 90 °C). The difference comes from insulation-rating temperature, the 80 % continuous-load adjustment (NEC) vs the Ca/Cg derating (IEC), and free-air vs raceway assumptions. Always design to the local code, never mix tables.

Ready for the full cable-sizing calculation?

Use the full AI Calculator to add voltage drop, short-circuit verification, protection coordination and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 157 engineering calculators · PDF report export