Skip to main content
NEC Table 310.16 · Verified

Wire Ampacity Chart & Calculator

Find the right circuit breaker or fuse for a load — applying the NEC 125% continuous-load rule and rounding to the next standard size in NEC 240.6.

125% rule
NEC 240.6 sizes
From A or W
Wire ampacity
100% Free
⚡ Open Full Electrical Calculator 📖 Read the Guide

In short — wire ampacity

Ampacity is the maximum current a conductor can carry continuously without exceeding its insulation temperature rating. In the US it comes from NEC (NFPA 70) Table 310.16.

The usable ampacity is not the number in the table. It is:

Usable ampacity = min( Table 310.16 value × Cambient × Cfill , termination limit )

  • Cambient — Table 310.15(B)(1), correcting from the 30 °C table basis.
  • Cfill — Table 310.15(C)(1), applied when more than three current-carrying conductors share a raceway.
  • Termination limit110.14(C)(1): 60 °C for equipment rated ≤100 A, 75 °C above.

Worked example. 1 AWG copper THHN, 30 °C ambient, 3 conductors, feeding a 125 A load. The 90 °C column says 145 A. But the breaker and lugs are 75 °C-rated, so 110.14(C) caps you at the 75 °C column: 130 A. That is your usable ampacity — and it still covers 125 A, so 1 AWG is correct. Size on the 90 °C column instead and you would have chosen 3 AWG (115 A), which is two sizes light at the terminals — where conductors actually overheat.

NEC Table 310.16 — wire ampacity chart

Allowable ampacity of insulated conductors rated up to 2000 V, not more than three current-carrying conductors in a raceway, cable or earth, based on an ambient temperature of 30 °C (86 °F). Correct for ambient and conductor count below, then apply the termination limit.

NEC Table 310.16 allowable ampacity, copper and aluminium, 60/75/90 °C
Size Copper Aluminium / Copper-clad Al
60 °C
TW, UF
75 °C
THW, THWN, XHHW
90 °C
THHN, THWN-2, XHHW-2
60 °C
TW, UF
75 °C
THW, THWN, XHHW
90 °C
THHN, THWN-2, XHHW-2
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350
600 kcmil350420475285340385
700 kcmil385460520315375425
750 kcmil400475535320385435
800 kcmil410490555330395445
900 kcmil435520585355425480
1000 kcmil455545615375445500

Read this before you use the 90 °C column. You almost never get to. NEC 110.14(C)(1) limits the conductor to the temperature rating of the terminal it lands on — 60 °C for equipment rated 100 A or less, 75 °C above that. The 90 °C column exists so you have headroom for derating; it is not the ampacity you may use. This is the single most common mistake made with this table, and most ampacity charts online do not mention it at all.

⚡ Wire Ampacity Calculator — with the termination limit

Pick a conductor and the calculator applies Table 310.16, the ambient and conduit-fill corrections, and the 110.14(C) termination cap — then tells you which one actually governs.

Table 310.16 value
After derating
Termination limit
Usable ampacity
Max OCPD
What governs

⚠️ NEC-based. Verify against the current edition and have a licensed electrician or engineer review before installation.

Standards & method

✓ Formula independently verified 12 July 2026
Governing standard
NEC (NFPA 70) Article 310
Clauses applied
  • Table 310.16 — allowable ampacity, Cu & Al, 60/75/90 °C
  • Table 310.15(B)(1) — ambient temperature correction
  • Table 310.15(C)(1) — adjustment for >3 current-carrying conductors
  • 110.14(C)(1) — termination temperature limit
  • 240.4(D) — small-conductor OCPD caps (14/12/10 AWG)
  • 240.6(A) — standard OCPD ratings
Core formula
Usable = min(Table 310.16 × C_ambient × C_fill, termination limit)
Independently verified
12 July 2026 — Table 310.16 transcribed and checked against the Code, and the derating and termination logic verified numerically against worked reference cases.

Why this matters: Almost every wire ampacity chart online publishes the 90 °C column without mentioning 110.14(C). A user who sizes from it gets a conductor that is legal on paper and undersized at the lug. This calculator applies the termination cap and tells you when it governs.

Results are for guidance. Verify against the current edition of the NEC and have a licensed electrician or engineer review before installation.

How to read the ampacity chart correctly

The table gives you three numbers per conductor. Only one of them is the answer, and it is almost never the biggest one.

The rule
Usable ampacity = min( Table 310.16 × Cambient × Cfill , termination limit )

Step 1 — find the table value

Look up the conductor in the chart above at its insulation temperature rating. THHN and XHHW-2 are 90 °C. THWN and XHHW are 75 °C. TW and UF are 60 °C.

Step 2 — correct for ambient (Table 310.15(B)(1))

The table assumes 30 °C (86 °F). A hot attic, a rooftop, or a boiler room will be higher, and the ampacity falls.

Step 3 — adjust for conduit fill (Table 310.15(C)(1))

More than three current-carrying conductors in the same raceway and the conductors cannot shed heat as easily. Four to six conductors: 80%. Seven to nine: 70%. Ten to twenty: 50%.

Step 4 — apply the termination limit (110.14(C)(1)) — this is the one people miss

A chain is as strong as its weakest link, and the weakest link in a conductor run is usually the lug it terminates on. Equipment rated 100 A or less is generally limited to the 60 °C column. Above 100 A, the 75 °C column. It does not matter that your THHN is rated 90 °C — if it lands on a 75 °C lug, you take the 75 °C ampacity.

The 90 °C column is not useless. It is what you derate from in steps 2 and 3, which often leaves you better off than starting at 75 °C. But whatever you derate to, you may never exceed the termination column.

The mistake this chart is designed to prevent

Take a 125 A load, 1 AWG copper THHN, 30 °C, three conductors in a conduit.

  • The 90 °C column says 145 A. Plenty of room. Many charts stop here.
  • But the breaker and its lugs are 75 °C-rated. NEC 110.14(C)(1) caps you at the 75 °C column: 130 A.
  • 130 A still covers 125 A, so 1 AWG is correct — but only because we checked.

Now run the same logic in reverse. If you had sized purely from the 90 °C column, 3 AWG (115 A) would have looked adequate for a 110 A load. On a 75 °C terminal, 3 AWG is only good for 100 A. You would be 10 A over at the lug — which is exactly where conductors overheat, because that is where the heat has nowhere to go.

Wire ampacity — frequently asked

What is wire ampacity?

Ampacity is the maximum current a conductor can carry continuously without its temperature exceeding the rating of its insulation. In the United States it is set by NEC (NFPA 70) Table 310.16 for conductors in a raceway, cable or earth.

Why can't I use the 90 °C ampacity column?

Because of NEC 110.14(C)(1). The conductor may be rated 90 °C, but the breaker lug or terminal it lands on is usually rated 60 °C (equipment 100 A or less) or 75 °C (above 100 A). The Code limits you to the ampacity column matching the lowest-rated part of the connection. The 90 °C column exists so you have headroom to derate from — it is not the ampacity you may use.

What is the ampacity of 6 AWG copper wire?

6 AWG copper: 55 A at 60 °C, 65 A at 75 °C, 75 A at 90 °C (NEC Table 310.16). In practice, on a 60 °C-rated terminal — which is typical for equipment rated 100 A or less — the usable ampacity is 55 A.

What is the ampacity of 2/0 copper wire?

2/0 copper: 145 A at 60 °C, 175 A at 75 °C, 195 A at 90 °C. Because 2/0 is normally used above 100 A, the 75 °C termination column applies and the usable ampacity is 175 A.

What is the ampacity of 4/0 aluminium wire?

4/0 aluminium: 150 A at 60 °C, 180 A at 75 °C, 205 A at 90 °C. On the 75 °C terminals typical above 100 A, the usable ampacity is 180 A. This is why 4/0 aluminium is the common choice for a 200 A residential service — 180 A after the 83% service-conductor allowance of 310.12 covers it.

How do I derate wire ampacity for ambient temperature?

Multiply the Table 310.16 value by the correction factor from Table 310.15(B)(1), which is based on a 30 °C (86 °F) ambient. For example, a 90 °C conductor at 45 °C ambient is multiplied by 0.87. Above roughly 55 °C ambient, 60 °C insulation can no longer be used at all.

What happens when more than three conductors share a conduit?

NEC 310.15(C)(1) applies an adjustment factor: 80% for 4–6 current-carrying conductors, 70% for 7–9, 50% for 10–20, 45% for 21–30, 40% for 31–40 and 35% above that. Neutrals that carry only unbalanced current, and equipment grounding conductors, are generally not counted.

Can the breaker be bigger than the wire ampacity?

Generally no — NEC 240.4 requires the overcurrent device to protect the conductor. 240.4(B) permits the next standard size up in limited cases (600 A or less, not a receptacle branch circuit), and 240.4(D) caps 14, 12 and 10 AWG copper at 15, 20 and 30 A regardless of what the table says.