Skip to main content
⚡ Machines & Generation

Motor Starter Sizing Calculator

From a motor's power, get the full-load current and the four parts of a starter: overload relay setting, contactor (AC-3) rating and short-circuit breaker (MCCB).

Overload setting
Contactor AC-3
MCCB / breaker
DOL & star-delta
100% Free
⚡ Open Full Electrical Calculator 📖 Read the Guide

Motor starter — Quick answer

Everything is referenced to the motor's full-load current (FLA): a high breaker for in-rush, a contactor to switch, and an overload set near FLA to protect the windings.

Overload ≈ FLA  |  Contactor (AC-3) ≥ FLA  |  MCCB ≈ 2.5 × FLA (NEC 430.52)

Worked example: An 11 kW, 415 V motor has FLA ≈ 20 A. Overload set ≈ 20 A, contactor 25 A AC-3, breaker ≈ 50 A MCCB. In a star-delta starter each contactor carries 0.58 × 20 = 11.6 A.

Starting methods at a glance

MethodStart currentStart torque
DOL6–8× FLA100%
Star-delta2–3× FLA≈ 33%
Soft starter3–4× FLAadjustable
VFD1–1.5× FLAfull, controlled

Used for: motor control centres, pump and fan panels, conveyor and compressor starters.

⚡ Motor Starter Sizing Calculator

Enter the motor nameplate. The starter parts are sized from the calculated full-load current.

Full-load current
Overload set
Contactor (AC-3)
MCCB / breaker

⚠️ Guide values. Overload setting follows NEC 430.32 (≈100–125% FLA by service factor); breaker per NEC 430.52. Confirm with device curves.

A motor starter has three jobs split across separate devices: a breaker or fuse for short-circuit protection, a contactor to switch the motor on and off, and an overload relay to protect the windings from sustained overload. All three are sized from the motor's full-load current. The breaker is set high so the starting in-rush doesn't trip it; the overload is set near full-load current; and the contactor must be rated for motor-switching (AC-3) duty.

Reviewed: June 19, 2026 · Author: Naveen P N, Founder — AI Calculator · Verified against: NEC (NFPA 70) Article 430, IEC 60947.

Safety notice. Motor protection is governed by detailed code rules (NEC 430, IEC 60947) that depend on motor type, service factor, duty and starter. These are first-pass guide values; final selection must use the device manufacturer's data and be verified by a licensed engineer. See our disclaimer.

How a starter is sized

Full-load current (3-phase)
FLA = (P / η) / (√3 × V × PF)
Overload relay
Set ≈ FLA (100–125% by service factor, NEC 430.32)
Contactor
AC-3 rating ≥ FLA  (star-delta: each contactor ≥ 0.58 × FLA)
Short-circuit breaker
MCCB ≈ 2.5 × FLA (inverse-time, ≤ 250% NEC 430.52)

The big gap between the overload (≈ FLA) and the breaker (≈ 2.5× FLA) is deliberate: the breaker must ignore the 6–8× starting in-rush, while the overload protects the windings during running. They guard against different faults.

Worked example — 11 kW DOL starter

Scenario: 11 kW, 415 V, 3-phase motor, PF 0.85, efficiency 90%, direct-on-line.

Full-load current
FLA = (11000 / 0.9) / (1.732 × 415 × 0.85) = 20 A

Overload set to about 20 A. Contactor: next AC-3 rating ≥ 20 A = 25 A. MCCB: 2.5 × 20 = 50 A → 50 A inverse-time breaker, which lets the ≈130 A in-rush pass at start but still protects against a short circuit. Get the FLA itself from the motor parameters calculator.

Frequently Asked Questions

How do I size a motor starter?

From the motor FLA: overload ≈ 100–115% FLA, contactor AC-3 ≥ FLA, breaker ≈ 2.5× FLA (NEC 430.52). For a 20 A motor: overload ≈ 20 A, contactor 25 A AC-3, breaker ≈ 50 A.

What rating of contactor do I need for a motor?

Use the AC-3 (motor duty) rating, at or above FLA. AC-3 ratings are lower than AC-1, so read the AC-3 column. In star-delta, each contactor carries about 58% of line current.

How do I set a motor overload relay?

Set the thermal overload to the nameplate FLA, adjusted for service factor — about 100% for SF 1.0 and up to 115–125% for higher SF (NEC 430.32). It protects against running overload, not short circuit.

Why is the motor breaker much larger than the overload?

The breaker only does short-circuit/ground-fault protection, so it is set high (≈250% FLA) to let the 6–8× starting in-rush pass. The overload, set near FLA, handles running overload. Different faults, different devices.

What is the difference between DOL and star-delta starting?

DOL connects full voltage — simplest, highest in-rush (6–8× FLA). Star-delta starts in star (≈⅓ current and torque) then switches to delta, cutting the surge. Soft starters and VFDs reduce in-rush further and electronically.

Ready to perform complete calculations?

Use the full AI Calculator suite for motor, cable and protection design with a PDF report.

⚡ Open Full Calculator — Free

No registration required · 350+ engineering calculators · PDF report export