Skip to main content
⚡ Protection & Distribution

Busbar Sizing Calculator

Find the copper or aluminium busbar cross-section for a continuous current, and check the short-circuit thermal minimum — then pick the next standard bar size.

Copper & aluminium
Current density
SC withstand
Standard bars
100% Free
⚡ Open Full Electrical Calculator 📖 Read the Guide

Busbar sizing — Quick answer

Pick the cross-section so the current density stays within limits, then check the short-circuit thermal minimum.

Continuous: A = I / J  |  Short circuit: Amin = Isc × √t / k  (k ≈ 143 Cu, 94 Al)

Worked example: 630 A on copper at 1.2 A/mm²: A = 630 / 1.2 = 525 mm², so a 100 × 6 mm bar (600 mm²) is the next standard size. A 25 kA / 1 s fault needs only 25,000 × √1 / 143 = 175 mm², so the continuous rating governs here.

Approximate copper busbar capacity (bare, still air)

Bar (W × T)Area≈ Capacity
25 × 5 mm125 mm²≈ 180 A
40 × 5 mm200 mm²≈ 280 A
50 × 6 mm300 mm²≈ 400 A
100 × 10 mm1000 mm²≈ 1250 A

Used for: switchboards, panel incomers, distribution boards, substation links, generator and battery bus.

⚡ Busbar Sizing Calculator

Enter the continuous current and material. Adjust the current density for your cooling, and add a fault current to check short-circuit withstand.

Continuous area
Short-circuit min
Governing area
Suggested bar

⚠️ Current density is an estimate — always confirm against the bar manufacturer's de-rated ampacity tables for your mounting and temperature.

A busbar is a solid metal bar that distributes current inside switchgear and distribution boards. Sizing it has two parts: the bar must carry the continuous current without exceeding its allowable temperature rise, and it must survive the short-circuit current for the time the protection takes to clear, without melting or deforming. The continuous part is handled with an allowable current density (amps per mm²); the short-circuit part with the adiabatic thermal equation. The larger of the two areas governs.

Reviewed: June 19, 2026 · Author: Naveen P N, Founder — AI Calculator · Verified against: IEC 61439, IEC 60865 (short-circuit effects), and copper-association busbar guides.

Engineering notice. Current density is a planning estimate; the real ampacity of a bar depends on its surface finish, orientation, spacing, enclosure and ambient temperature. Final busbar selection must use the manufacturer's de-rated tables and a verified short-circuit study. See our disclaimer.

Continuous current — the current-density method

The simplest first estimate divides the current by an allowable current density:

Required area
A (mm²) = I (A) / J (A/mm²)

Typical conservative design densities for bare bars in still air are about 1.2–1.6 A/mm² for copper and 0.8–1.0 A/mm² for aluminium. Larger bars run a little cooler per unit area, and forced ventilation raises the figure, so always confirm against the manufacturer's ampacity tables for the actual bar size, mounting and temperature.

Short-circuit withstand — the adiabatic equation

During a fault the bar heats almost instantly, so the check assumes no heat escapes (adiabatic). The minimum cross-section is:

Thermal minimum area
Amin = Isc × √t / k

Here Isc is the RMS fault current in amps, t is the clearing time in seconds, and k is a material constant (about 143 for copper and 94 for aluminium for common start/finish temperatures). Get the fault current from the fault current calculator. The bar you choose must satisfy both the continuous-current area and this thermal minimum.

Worked example — 800 A switchboard incomer

Scenario: An 800 A copper busbar, fault level 30 kA for 0.5 s.

Continuous area (J = 1.3 A/mm²)
A = 800 / 1.3 = 615 mm²
Short-circuit minimum
Amin = 30,000 × √0.5 / 143 = 30,000 × 0.707 / 143 = 148 mm²

The continuous area (615 mm²) governs, so a 80 × 8 mm bar (640 mm²) is the next standard size that satisfies both checks. The short-circuit requirement is comfortably met.

Frequently Asked Questions

How do you size a busbar for current?

Divide current by an allowable density: area (mm²) = current (A) ÷ density (A/mm²). Bare copper in still air is about 1.2–1.6 A/mm²; aluminium 0.8–1.0. For 630 A copper at 1.2: 525 mm², so a 100 × 6 mm bar (600 mm²) is the next standard size.

What current density is used for copper busbar?

Roughly 1.2–1.6 A/mm² for bare copper in still air, higher with forced cooling. Aluminium carries about two-thirds of copper (0.8–1.0 A/mm²). Always confirm against the manufacturer's de-rated tables.

How do I check busbar short-circuit withstand?

Use Amin = Isc × √t ÷ k, with Isc in amps, t in seconds, k ≈ 143 (copper) or 94 (aluminium). The chosen bar must meet both the continuous-current area and this thermal minimum.

Why is copper better than aluminium for busbars?

Copper has higher conductivity, so it needs a smaller cross-section and runs cooler for the same current. Aluminium is lighter and cheaper but needs about 50–60% more area and careful jointing against oxidation.

Does busbar ampacity depend on temperature?

Yes. It is set by the allowable temperature rise (typically 50–65 °C over ambient). Higher ambient, enclosed mounting or closely-stacked bars all reduce the allowable current, so de-rating factors apply.

Ready to perform complete calculations?

Use the full AI Calculator suite for fault current, breakers and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 350+ engineering calculators · PDF report export