⚡ AS/NZS 3008.1.1 · Australia / New Zealand

AS/NZS 3008 Cable Sizing Calculator

AS/NZS 3008.1.1:2017 cable sizing for Australian and New Zealand installations. Compute minimum mm² with Table 3 derating factors, voltage-drop check and harmonisation with AS/NZS 3000:2018 wiring rules.

Standard-Verified
Worked Example
Free · No Login

In short — as/nzs 3008.1.1 cable sizing

AS/NZS 3008.1.1 Cable Sizing selects the minimum standard cable cross-section whose corrected ampacity Iz exceeds the design current Ib. Per AS/NZS 3008.1.1 Table 4 / Column 11 (75 °C V90 thermoplastic, in conduit):

It = Ib ÷ (Ca × Cg × Ci)   →   pick smallest cable where Iz ≥ It

Worked example: Ib = 25 A, Method C, ambient correction Ca = 0.94, no grouping  →  It = 25 ÷ (0.94 × 1.00) = 26.6 A → 2.5 mm² (Iz = 30 A ≥ 26.6 A). Selected cable: 2.5 mm² copper (≈ 12 AWG).

Standard: AS/NZS 3008.1.1 Table 4 / Column 11 (75 °C V90 thermoplastic, in conduit).

Used for: Australian and New Zealand residential, commercial and industrial installations; ASNZ wiring rules compliance; mining and remote-area installations.

⚡ AS/NZS 3008 Cable Sizing — Quick Estimator

Pre-loaded with defaults for Installation condition X — single-core in air-filled conduit on a wall. Edit any field to recompute.

Required It (A)
Minimum Cable Size
Cable Ampacity Iz
Derating Applied

⚠️ Estimate based on copper / XLPE conductors per IEC 60364-5-52 Table B.52.4. Use the full calculator for voltage drop, short-circuit and protection coordination.

AS/NZS 3008.1.1 Cable Sizing — Method

AS/NZS 3008.1.1:2017 is the joint Australia / New Zealand standard for cable selection and ampacity, used together with AS/NZS 3000:2018 (the Wiring Rules). The method mirrors IEC 60364-5-52 — pick a cable whose tabulated Iz ≥ Ib after Ca, Cg, Ci correction — but tables are recalculated for V75/V90/X-90 insulations and Australian ambient (typically 40 °C reference). Voltage drop limit is 5 % from main switchboard to the load.

Required tabulated current
It = Ib ÷ (Ca × Cg × Ci)

Where:

  • Ib — design current of the circuit (A), from the load calculation
  • Ca — ambient temperature correction (1.00 at 30 °C reference)
  • Cg — grouping / bunching factor (1.00 for a single circuit)
  • Ci — thermal-insulation factor (1.00 if the cable is in free air; 0.50 if fully buried in insulation)

Then pick the smallest cable cross-section in AS/NZS 3008.1.1 Table 4 / Column 11 (75 °C V90 thermoplastic, in conduit) whose tabulated ampacity Iz ≥ It.

Related cable sizing calculators

Other standard- and method-specific cable-sizing calculators in the same series — same procedure, different reference tables and defaults:

Frequently Asked Questions

What is the difference between AS/NZS 3000 and AS/NZS 3008?

AS/NZS 3000:2018 is the Wiring Rules — the regulatory standard saying what is allowed (clearances, RCD requirements, equipotential bonding, 5 % voltage-drop limit). AS/NZS 3008.1.1:2017 is the cable selection standard — the look-up tables and methods that tell you which cable size satisfies AS/NZS 3000's electrical requirements. Together they replace the older AS 3008 and SAA Wiring Rules.

Which AS/NZS 3008 table do I use?

Tables 3, 4, 5, 6 of AS/NZS 3008.1.1 give current-carrying capacities for copper conductors with V75, V90, R-HF-90 and X-90 insulations; Tables 9–12 do the same for aluminium. Each table has columns for installation conditions A–T (in air, in conduit, on tray, buried, etc.). The reference ambient for Aus is 40 °C above ground and 25 °C below ground (NZ uses 30 °C above).

What ambient temperature does AS/NZS 3008 reference?

40 °C for cables installed in air (above ground) and 25 °C for cables direct-buried below ground. New Zealand uses 30 °C for above-ground cables. If the actual ambient differs, apply Ca from Table 27 (e.g. 0.91 at 45 °C, 0.82 at 50 °C for V90 insulation in air).

How is voltage drop calculated under AS/NZS 3008?

Vd = Vc × I × L / 1000, where Vc is the conductor 'mV/A·m' value from Tables 40–47, I is the design current and L is the run length. AS/NZS 3000 Clause 3.6 caps Vd at 5 % of nominal voltage between the point of supply and any consumer outlet. For three-phase circuits use the line-to-line value of Vc.

How does AS/NZS 3008 handle short-circuit cable sizing?

AS/NZS 3008.1.1 Section 5 / Equation 5.1: t × I_sc² ≤ K² × S² where K = 111 (V75 Cu), 143 (X-90 Cu), 74 (V75 Al), 94 (X-90 Al), I_sc is the prospective short-circuit current and t is the protective device's clearing time. The selected cable must satisfy both ampacity and short-circuit withstand.

Is AS/NZS 3008 the same as IEC 60364-5-52?

Methodology yes (Iz × Ca × Cg × Ci ≥ Ib), tables no. AS/NZS uses different reference ambients (40 °C vs 30 °C), different installation-condition labels (A–T vs A1–E) and different K values for short-circuit. A cable sized to AS/NZS 3008 is generally accepted in IEC jurisdictions, but not necessarily vice-versa — always size to the local code.

Ready for the full cable-sizing calculation?

Use the full AI Calculator to add voltage drop, short-circuit verification, protection coordination and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 157 engineering calculators · PDF report export