← Cable Sizing Calculator (all standards)
⚡ AS/NZS 3008.1.1 · Australia / New Zealand

AS/NZS 3008 Cable Sizing Calculator

⚠️ This calculator does not implement the AS/NZS 3008 tables.
It computes current-carrying capacity from IEC 60364-5-52. The two standards are built on different assumptions — most importantly soil thermal resistivity (AS/NZS assumes 1.2 K·m/W for direct burial; IEC assumes 2.5 K·m/W), different installation-method codes, and different insulation designations (V-75 / V-90 / X-90).

The results will be close, but they are not AS/NZS values and cannot support an AS/NZS compliance certificate. We cannot tell you the exact size or direction of the discrepancy, because we do not hold the AS/NZS 3008 tables — and that uncertainty is precisely why we will not publish this as an AS/NZS calculator.

For AS/NZS 3008 design, size directly from AS/NZS 3008.1.1. We would rather say this than publish a number we cannot stand behind.

AS/NZS 3008.1.1:2017 cable sizing for Australian and New Zealand installations. Compute minimum mm² with Table 3 derating factors, voltage-drop check and harmonisation with AS/NZS 3000:2018 wiring rules.

Standard-Verified
Worked Example
Free · No Login

In short — as/nzs 3008.1.1 cable sizing

AS/NZS 3008.1.1 Cable Sizing selects the minimum standard cable cross-section whose corrected ampacity Iz exceeds the design current Ib. Per AS/NZS 3008.1.1 Table 4 / Column 11 (75 °C V90 thermoplastic, in conduit):

It = Ib ÷ (Ca × Cg × Ci)   →   pick smallest cable where Iz ≥ It

Worked example: Ib = 25 A, Method C, ambient correction Ca = 0.94, no grouping  →  It = 25 ÷ (0.94 × 1.00) = 26.6 A → 2.5 mm² (Iz = 30 A ≥ 26.6 A). Selected cable: 2.5 mm² copper (≈ 12 AWG).

Standard: AS/NZS 3008.1.1 Table 4 / Column 11 (75 °C V90 thermoplastic, in conduit).

Used for: Australian and New Zealand residential, commercial and industrial installations; ASNZ wiring rules compliance; mining and remote-area installations.

⚡ Cable Sizing Calculator — Full Engine

Standards-based sizing: ampacity with temperature & grouping derating, voltage drop over the run length, short-circuit (adiabatic) check and protective-device coordination. Enter every parameter for a complete result.

Calculation basis — please read. This tool computes to IEC 60364-5-52 (ampacity Table B.52.4, correction factors B.52.14 / B.52.17, results in mm²). It does not use the AS/NZS 3008.1.1 Table 4 current-carrying capacities, the AS/NZS installation-method codes, or the AS/NZS Table 40–51 Vc (mV/A/m) voltage-drop tables. The two standards give similar but not identical answers, and AS/NZS uses a 5% total voltage-drop limit measured from the point of supply. For work certified to AS/NZS 3008, size from the standard and have a licensed electrical worker sign off. We would rather tell you this than hand you a number that looks authoritative and isn't.
Design Current Ib
Required It
Recommended Size
Derated Iz
Voltage Drop
Governing Criterion

⚠️ Standards-based estimate. Verify against the current edition and have a licensed engineer review before construction.

Standards & method

✓ Independently verified 12 July 2026
What this page actually computes
IEC 60364-5-52 — Table B.52.4 ampacity, Table B.52.14 ambient correction, Table B.52.17 grouping, IEC 60364-4-43 §433.1. The AS/NZS 3008 tables are NOT implemented.
Why we say so
AS/NZS 3008.1.1 and IEC 60364-5-52 use different reference ambients (40 °C vs 30 °C air), different soil thermal resistivity (1.2 vs 2.5 K·m/W), different installation-method codes and different insulation designations. This engine applies IEC corrections from the IEC datum — internally consistent, but not AS/NZS. The two standards make different assumptions — soil thermal resistivity above all — so the results differ by an amount we cannot quantify without the AS/NZS tables. Cable sizing is safety-critical, so we state the basis rather than imply a compliance we have not implemented.
Core formula
Iz = Iz_table(IEC) × Ca × Cg  ·  ΔV = k·I·(R·cosφ + X·sinφ)·L / 1000
Independently verified
12 July 2026 — the IEC engine is verified against IEC 60364-5-52 worked cases. The AS/NZS claim is not verified, because it is not implemented.

For AS/NZS 3008 compliance, size directly from AS/NZS 3008.1.1 and have a licensed electrical engineer review before installation.

AS/NZS 3008.1.1 Cable Sizing — Method

AS/NZS 3008.1.1:2017 is the joint Australia / New Zealand standard for cable selection and ampacity, used together with AS/NZS 3000:2018 (the Wiring Rules). The method mirrors IEC 60364-5-52 — pick a cable whose tabulated Iz ≥ Ib after Ca, Cg, Ci correction — but tables are recalculated for V75/V90/X-90 insulations and Australian ambient (typically 40 °C reference). Voltage drop limit is 5 % from main switchboard to the load.

Required tabulated current
It = Ib ÷ (Ca × Cg × Ci)

Where:

  • Ib — design current of the circuit (A), from the load calculation
  • Ca — ambient temperature correction (1.00 at 30 °C reference)
  • Cg — grouping / bunching factor (1.00 for a single circuit)
  • Ci — thermal-insulation factor (1.00 if the cable is in free air; 0.50 if fully buried in insulation)

Then pick the smallest cable cross-section in AS/NZS 3008.1.1 Table 4 / Column 11 (75 °C V90 thermoplastic, in conduit) whose tabulated ampacity Iz ≥ It.

Related cable sizing calculators

Other standard- and method-specific cable-sizing calculators in the same series — same procedure, different reference tables and defaults:

💡 Sizing the earth / protective conductor? Use the dedicated Earthing Cable Size Calculator — BS 7671 Table 54.7, IEC 60364-5-54, NEC 250.122.

Frequently Asked Questions

What is the difference between AS/NZS 3000 and AS/NZS 3008?

AS/NZS 3000:2018 is the Wiring Rules — the regulatory standard saying what is allowed (clearances, RCD requirements, equipotential bonding, 5 % voltage-drop limit). AS/NZS 3008.1.1:2017 is the cable selection standard — the look-up tables and methods that tell you which cable size satisfies AS/NZS 3000's electrical requirements. Together they replace the older AS 3008 and SAA Wiring Rules.

Which AS/NZS 3008 table do I use?

Tables 3, 4, 5, 6 of AS/NZS 3008.1.1 give current-carrying capacities for copper conductors with V75, V90, R-HF-90 and X-90 insulations; Tables 9–12 do the same for aluminium. Each table has columns for installation conditions A–T (in air, in conduit, on tray, buried, etc.). The reference ambient for Aus is 40 °C above ground and 25 °C below ground (NZ uses 30 °C above).

What ambient temperature does AS/NZS 3008 reference?

40 °C for cables installed in air (above ground) and 25 °C for cables direct-buried below ground. New Zealand uses 30 °C for above-ground cables. If the actual ambient differs, apply Ca from Table 27 (e.g. 0.91 at 45 °C, 0.82 at 50 °C for V90 insulation in air).

How is voltage drop calculated under AS/NZS 3008?

Vd = Vc × I × L / 1000, where Vc is the conductor 'mV/A·m' value from Tables 40–47, I is the design current and L is the run length. AS/NZS 3000 Clause 3.6 caps Vd at 5 % of nominal voltage between the point of supply and any consumer outlet. For three-phase circuits use the line-to-line value of Vc.

How does AS/NZS 3008 handle short-circuit cable sizing?

AS/NZS 3008.1.1 Section 5 / Equation 5.1: t × I_sc² ≤ K² × S² where K = 111 (V75 Cu), 143 (X-90 Cu), 74 (V75 Al), 94 (X-90 Al), I_sc is the prospective short-circuit current and t is the protective device's clearing time. The selected cable must satisfy both ampacity and short-circuit withstand.

Is AS/NZS 3008 the same as IEC 60364-5-52?

Methodology yes (Iz × Ca × Cg × Ci ≥ Ib), tables no. AS/NZS uses different reference ambients (40 °C vs 30 °C), different installation-condition labels (A–T vs A1–E) and different K values for short-circuit. A cable sized to AS/NZS 3008 is generally accepted in IEC jurisdictions, but not necessarily vice-versa — always size to the local code.

Ready for the full cable-sizing calculation?

Use the full AI Calculator to add voltage drop, short-circuit verification, protection coordination and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 350+ engineering calculators · PDF report export