⚡ Three-Phase · 400 V / 415 V / 480 V

Three-Phase Cable Sizing Calculator

Cable sizing for 3-phase 400 V, 415 V or 480 V circuits and sub-mains. Computes the minimum line-conductor cross-section, neutral sizing for unbalanced or harmonic loads (per BS 7671 524.2.3 / IEC 60364), and earth conductor.

Standard-Verified
Worked Example
Free · No Login

In short — three-phase circuit cable sizing

Three-Phase Circuit Cable Sizing selects the minimum standard cable cross-section whose corrected ampacity Iz exceeds the design current Ib. Per IEC 60364-5-52 Table B.52.4, Method B1 (3-core in conduit on wall):

It = Ib ÷ (Ca × Cg × Ci)   →   pick smallest cable where Iz ≥ It

Worked example: Ib = 63 A, Method B1, ambient 30 °C (Ca = 1.00), grouping Cg = 0.80  →  It = 63 ÷ (1.00 × 0.80) = 78.8 A → 16 mm² (Iz = 85 A ≥ 78.8 A). Selected cable: 16 mm² copper (≈ 4 AWG).

Standard: IEC 60364-5-52 Table B.52.4, Method B1 (3-core in conduit on wall).

Used for: industrial motor circuits and sub-mains; commercial three-phase distribution; data-centre power feeds; HVAC chiller and lift supplies; switchroom inter-board cables.

⚡ Three-Phase Cable Sizing — Quick Estimator

Pre-loaded with defaults for Three-phase 400 V circuit, 4-core. Edit any field to recompute.

Required It (A)
Minimum Cable Size
Cable Ampacity Iz
Derating Applied

⚠️ Estimate based on copper / XLPE conductors per IEC 60364-5-52 Table B.52.4. Use the full calculator for voltage drop, short-circuit and protection coordination.

Three-Phase Circuit Cable Sizing — Method

Three-phase circuits — 400 V (Europe / IEC), 415 V (UK / older Australia), 480 V (US industrial) — power most motors, sub-mains and commercial loads. Cable sizing follows the same Iz × Ca × Cg × Ci ≥ Ib procedure but uses the line current Ib = P / (√3 × V × cosφ × η). The neutral can be reduced for balanced loads ≥ 16 mm² (IEC 524.2.3) but must be full-size or larger for harmonic-rich loads (variable-speed drives, LED lighting, IT loads), per BS 7671 524.2.4.

Required tabulated current
It = Ib ÷ (Ca × Cg × Ci)

Where:

  • Ib — design current of the circuit (A), from the load calculation
  • Ca — ambient temperature correction (1.00 at 30 °C reference)
  • Cg — grouping / bunching factor (1.00 for a single circuit)
  • Ci — thermal-insulation factor (1.00 if the cable is in free air; 0.50 if fully buried in insulation)

Then pick the smallest cable cross-section in IEC 60364-5-52 Table B.52.4, Method B1 (3-core in conduit on wall) whose tabulated ampacity Iz ≥ It.

Related cable sizing calculators

Other standard- and method-specific cable-sizing calculators in the same series — same procedure, different reference tables and defaults:

Frequently Asked Questions

How is three-phase cable sizing different from single-phase?

The design current uses Ib = P / (√3 × V_LL × cosφ × η) instead of Ib = P / (V × cosφ). Once Ib is computed, the cable sizing procedure (Iz × Ca × Cg × Ci ≥ Ib) is identical. Voltage drop is 1/√3 of single-phase for the same conductor size and current — so 3-phase cables can be smaller for the same kW transferred over the same distance.

Can I reduce the neutral cross-section in a three-phase cable?

For balanced linear loads (no significant 3rd harmonic) and line conductor ≥ 16 mm² Cu / 25 mm² Al: yes — the neutral can be ~50 % of the line per IEC 60364-5-52 524.3 / BS 7671 524.2.3. For loads with > 15 % 3rd-harmonic content (LED lighting, VSDs, computers, switchmode supplies), the neutral can carry up to 1.7× the line current and must be sized accordingly — often requiring a 'high-neutral' cable with 200 % neutral.

How is three-phase voltage drop calculated?

Vd = √3 × I × L × (R cosφ + X sinφ) / 1000 (V). For the same conductor and current, Vd is 1/√3 ≈ 0.577 of an equivalent single-phase circuit (which uses 2× the per-line drop). Convert to percentage: % Vd = Vd / V_LL × 100. Limit is 5 % per IEC / BS 7671 / 3 % per NEC for branch circuits.

How do I size a cable for a three-phase motor?

Use the motor full-load current (FLA) from the nameplate (not the calculated kW/√3·V·PF·η — actual FLA accounts for slip and inefficiency). NEC requires conductors sized to 125 % of motor FLA (Article 430.22). IEC / BS 7671 require the cable to safely carry the FLA continuously and the starting current (typically 6–7× FLA) for the start duration without thermal damage — the adiabatic equation S² ≥ I²t / k² governs.

What size cable do I need for a 63 A three-phase circuit?

63 A 3-phase in conduit on a wall (Method B1) at 30 °C with 3 circuits grouped: It = 63 / 0.80 = 78.75 A. From IEC 60364-5-52 Table B.52.4 (XLPE Cu): 16 mm² = 85 A ≥ 78.75 A ✅. Select 16 mm² 4-core XLPE/PVC SWA cable, MCB rated 63 A. Check voltage drop separately for runs > 30 m.

What is the earth (PE) cross-section for a three-phase cable?

For line conductors ≤ 16 mm² Cu: PE = line size (BS 7671 Table 54.7). For 16–35 mm² line: PE = 16 mm². For > 35 mm² line: PE = line/2 (minimum 16 mm²). NEC Table 250.122: 6 AWG PE for 100 A, 4 AWG for 200 A, 1/0 AWG for 400 A, 250 kcmil for 800 A. Always verify with the adiabatic equation for the prospective fault current and disconnection time.

Ready for the full cable-sizing calculation?

Use the full AI Calculator to add voltage drop, short-circuit verification, protection coordination and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 157 engineering calculators · PDF report export