← Cable Sizing Calculator (all standards)
Skip to main content
🟧 Copper · Cu Conductor

Copper Cable Sizing Calculator

Cable sizing calculator for copper conductors specifically. Compute minimum Cu cross-section using IEC / NEC / BS 7671 ampacity tables — copper is the default conductor for circuits up to ~120 mm² where current density and voltage drop both favour Cu over aluminium.

Standard-Verified
Worked Example
Free · No Login

In short — copper conductor cable sizing

Copper Conductor Cable Sizing selects the minimum standard cable cross-section whose corrected ampacity Iz exceeds the design current Ib. Per IEC 60364-5-52 Table B.52.4 (copper, XLPE, Reference Method B1):

It = Ib ÷ (Ca × Cg × Ci)   →   pick smallest cable where Iz ≥ It

Worked example: Ib = 40 A, Method B1, ambient 30 °C (Ca = 1.00), grouping Cg = 0.80  →  It = 40 ÷ (1.00 × 0.80) = 50.0 A → 10 mm² (Iz = 63 A ≥ 50.0 A). Selected cable: 10 mm² copper (≈ 6 AWG).

Standard: IEC 60364-5-52 Table B.52.4 (copper, XLPE, Reference Method B1).

Used for: branch and sub-main circuits up to 120 mm²; conduit-installed wiring; control circuits; data-centre power; medical and life-safety circuits where Cu's lower failure rate is required.

⚡ Cable Sizing Calculator — Full Engine

Standards-based sizing: ampacity with temperature & grouping derating, voltage drop over the run length, short-circuit (adiabatic) check and protective-device coordination. Enter every parameter for a complete result.

Design Current Ib
Required It
Recommended Size
Derated Iz
Voltage Drop
Governing Criterion

⚠️ Standards-based estimate. Verify against the current edition and have a licensed engineer review before construction.

Standards & method

✓ Independently verified 12 July 2026
Governing standard
IEC 60364-5-52
Clauses applied
Table B.52.4 ampacity (separate 2- and 3-loaded-conductor columns) · Table B.52.14 ambient correction · Table B.52.17 grouping correction · IEC 60364-4-43 §433.1 (Ib ≤ In ≤ Iz and I₂ ≤ 1.45·Iz) · voltage drop from IEC 60228 conductor resistance with BS 7671 App.4 reactance
Core formula
Iz = Iz_table × Ca × Cg  ·  ΔV = k·I·(R·cosφ + X·sinφ)·L / 1000
Why this matters
Three-phase circuits use the 3-loaded-conductor column, not the single-phase table. Voltage drop includes reactance and power factor — a resistance-only mV/A/m figure under-states the drop by ~32% at 300 mm², pf 0.85, and selects a conductor one size too small.
Independently verified
12 July 2026 — Re-derived from the governing standard and checked numerically against worked reference cases from the standard itself — not merely tested for “returns a number”.

Results are for guidance. Verify against the current edition of the governing standard and have a licensed engineer review before construction or installation.

Copper Conductor Cable Sizing — Method

Copper is the default conductor material for cables up to ~120 mm² in branch circuits, sub-mains and most industrial wiring. It has lower resistivity (16.78 nΩ·m vs 26.5 nΩ·m for Al), better creep resistance at terminations and longer service life. The trade-off is cost and weight — for cables ≥ 95 mm² and long runs, aluminium becomes economically competitive even with the larger cross-section it needs.

Required tabulated current
It = Ib ÷ (Ca × Cg × Ci)

Where:

  • Ib — design current of the circuit (A), from the load calculation
  • Ca — ambient temperature correction (1.00 at 30 °C reference)
  • Cg — grouping / bunching factor (1.00 for a single circuit)
  • Ci — thermal-insulation factor (1.00 if the cable is in free air; 0.50 if fully buried in insulation)

Then pick the smallest cable cross-section in IEC 60364-5-52 Table B.52.4 (copper, XLPE, Reference Method B1) whose tabulated ampacity Iz ≥ It.

Related cable sizing calculators

Other standard- and method-specific cable-sizing calculators in the same series — same procedure, different reference tables and defaults:

Frequently Asked Questions

Why is copper preferred over aluminium for small cables?

Below ~50 mm² aluminium becomes mechanically fragile, harder to terminate reliably, and the size penalty (~1.5× larger Cu cross-section for the same current) costs more in conduit and labour than the copper saves in metal. Most national codes (NEC 110.14, BS 7671 526) require AL-rated terminations and anti-oxidant compound, adding labour cost. For cables under 50 mm² copper is almost always the lower total-cost choice.

How does copper conductor ampacity compare to aluminium?

Aluminium has roughly 60–65 % the ampacity of copper for the same cross-section. Examples (IEC 60364-5-52 Method B1 XLPE): 16 mm² Cu = 85 A, 16 mm² Al = 67 A; 50 mm² Cu = 168 A, 50 mm² Al = 132 A. To match the same current as Cu, aluminium typically needs the next or next-but-one IEC standard size (e.g. 50 mm² Cu ≈ 70 mm² Al).

What is the resistance of a copper cable?

At 20 °C, hard-drawn copper has resistivity 17.24 nΩ·m, giving a per-metre resistance: 1.5 mm² = 12.1 mΩ/m, 2.5 mm² = 7.41 mΩ/m, 6 mm² = 3.08 mΩ/m, 16 mm² = 1.15 mΩ/m, 50 mm² = 0.387 mΩ/m. At 70 °C operating temperature, multiply by 1.20 (the temperature coefficient). Reactance for single-core XLPE is typically 0.08–0.10 mΩ/m.

Does copper cable need any special derating in groups?

No — Cu and Al follow the same Cg grouping factors from IEC Table B.52.17 (0.80 for 3 circuits, 0.70 for 6 circuits, etc.). The thermal model for grouping derating depends on insulation and air gap, not conductor material. The Iz starting point is different for Cu vs Al, but the multipliers are identical.

Can I splice copper to aluminium safely?

Only with bi-metallic compression connectors (CuAl, listed for the application) and inhibitor compound. The dissimilar-metal galvanic risk and the differential thermal-expansion creep make a direct Cu-Al connection a top cause of overheating fires (NEC 110.14, BS 7671 526.2). Cu-only or Al-only joints with the correct CSA are always preferable.

How much current can a 25 mm² copper cable carry?

Per IEC 60364-5-52 Table B.52.4 (XLPE/EPR, 30 °C, no grouping): 25 mm² Cu carries 99 A in Method A1, 112 A in B1, 119 A in C, 121 A in D1. PVC (70 °C) values are ~10 % lower. After typical derating (Ca 0.87 × Cg 0.80) the working ampacity drops to roughly 78 A in B1 — adequate for a 63 A protective device.

Ready for the full cable-sizing calculation?

Use the full AI Calculator to add voltage drop, short-circuit verification, protection coordination and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 350+ engineering calculators · PDF report export