⚡ BS 7671:2018+A2 · UK / NICEIC

BS 7671 Cable Sizing Calculator

BS 7671 (IET Wiring Regulations 18th Edition) cable sizing for UK installations. Compute minimum mm² per Appendix 4 reference method, with Ca, Cg, Ci correction factors and 3 % / 5 % voltage drop limits.

Standard-Verified
Worked Example
Free · No Login

In short — bs 7671:2018+a2 (niceic) cable sizing

BS 7671:2018+A2 (NICEIC) Cable Sizing selects the minimum standard cable cross-section whose corrected ampacity Iz exceeds the design current Ib. Per BS 7671 Appendix 4 Table 4D2A (single-core PVC, Ref Method B):

It = Ib ÷ (Ca × Cg × Ci)   →   pick smallest cable where Iz ≥ It

Worked example: Ib = 32 A, Method B1, ambient 30 °C (Ca = 1.00), 1 circuit (Cg = 1.00)  →  It = 32 ÷ (1.00 × 1.00) = 32.0 A → from BS 7671 Appendix 4 Table 4D2A (single-core PVC, Ref Method B): 4 mm² (Iz = 36 A). Selected cable: 4 mm² copper (≈ 10 AWG).

Standard: BS 7671 Appendix 4 Table 4D2A (single-core PVC, Ref Method B).

Used for: UK domestic, commercial and industrial wiring; NICEIC certified installations; landlord EICR remediation; new dwellings under Part P.

⚡ BS 7671 Cable Sizing — Quick Estimator

Pre-loaded with defaults for Reference Method B — single-core PVC/PVC in conduit on a wall. Edit any field to recompute.

Required It (A)
Minimum Cable Size
Cable Ampacity Iz
Derating Applied

⚠️ Estimate based on copper / XLPE conductors per IEC 60364-5-52 Table B.52.4. Use the full calculator for voltage drop, short-circuit and protection coordination.

BS 7671:2018+A2 (NICEIC) Cable Sizing — Method

BS 7671:2018+A2:2022 (IET Wiring Regulations, 18th Edition) is the UK national wiring code, certified by NICEIC, NAPIT, ELECSA and STROMA. Cable sizing follows Appendix 4 — pick the row from Tables 4D1A–4J5A (selected by conductor material, insulation, reference method and number of cores), apply Ca, Cg, Ci correction factors, then verify voltage drop and 0.4 s / 5 s disconnection.

Required tabulated current
It = Ib ÷ (Ca × Cg × Ci)

Where:

  • Ib — design current of the circuit (A), from the load calculation
  • Ca — ambient temperature correction (1.00 at 30 °C reference)
  • Cg — grouping / bunching factor (1.00 for a single circuit)
  • Ci — thermal-insulation factor (1.00 if the cable is in free air; 0.50 if fully buried in insulation)

Then pick the smallest cable cross-section in BS 7671 Appendix 4 Table 4D2A (single-core PVC, Ref Method B) whose tabulated ampacity Iz ≥ It.

Related cable sizing calculators

Other standard- and method-specific cable-sizing calculators in the same series — same procedure, different reference tables and defaults:

Frequently Asked Questions

Which BS 7671 table do I use for cable sizing?

Tables 4D1A–4J5A in Appendix 4. Most common: 4D2A (single-core 70 °C PVC, methods A–E), 4D5 (multi-core 70 °C PVC), 4E2A (90 °C thermosetting). The 'A' tables give tabulated current-carrying capacity Iz; 'B' tables give voltage drop in mV/A/m.

How do I apply BS 7671 correction factors?

From Appendix 4: Ca (ambient temperature, Table 4B1 — 0.87 at 40 °C for PVC), Cg (grouping, Table 4C1 — 0.80 for 3 circuits enclosed), Ci (thermal insulation, Table 52.2 in BS 7671 — 0.5 if fully buried in insulation > 0.5 m). Required tabulated current It = Ib / (Ca × Cg × Ci). Then pick a cable whose Iz ≥ It.

What voltage-drop limit does BS 7671 set?

BS 7671 Table 4Ab: 3 % for lighting and 5 % for power circuits, measured from the origin of the installation to any consuming point. For installations supplied directly from the public network, the same limit applies to the whole installation. For HV installations or longer runs, refer to BS 7671 Section 525.

Does BS 7671 require a maximum Zs disconnection check?

Yes. BS 7671 Tables 41.2–41.4 give the maximum earth-fault loop impedance Zs that ensures disconnection within the required time (0.4 s for 32 A or below in TN systems; 5 s for distribution circuits). Cable size and length, breaker characteristic (B/C/D) and circuit Zs together must satisfy this check, often more restrictive than ampacity.

What is the difference between BS 7671 and BS 7671:2018+A2?

Amendment 2 (March 2022) added: mandatory AFDDs in HMOs, hotels, care facilities and student accommodation (Section 421.1.7); revised Section 411 and 722 EV-charger requirements; updated Surge Protection Device (SPD) coordination; expanded use of low-smoke and halogen-free cable in escape routes. Cable-sizing tables are unchanged from 2018.

How does NICEIC inspect cable sizing on a Part P installation?

NICEIC inspectors verify on the Electrical Installation Certificate (EIC): correct cable type for the location, correct CSA from BS 7671 Appendix 4, voltage-drop calculation, Zs measurement vs Table 41 limit, RCD type & rating, and segregation from Cat-5/data cable per BS 6701. The cable-sizing calculator can populate the EIC's design-data section.

Ready for the full cable-sizing calculation?

Use the full AI Calculator to add voltage drop, short-circuit verification, protection coordination and a professional PDF report.

⚡ Open Full Calculator — Free

No registration required · 157 engineering calculators · PDF report export