Skip to main content
β˜€οΈ Solar & Energy Β· NEC 690

Solar Inverter Sizing Calculator

From total continuous AC load and array DC kW, get the recommended inverter rating and the DC/AC ratio.

Inverter Rating
DC/AC Ratio
Continuous Load

Solar inverter sizing — Quick answer

Size the inverter to the continuous AC load × 1.25, keeping the array within the inverter’s DC/AC ratio (about 1.1–1.3).

⚑ Solar Inverter Sizing Calculator

Recommended inverter rating from the AC load, plus DC/AC ratio if you enter the array size.

Min Continuous
β€”
Recommended Inverter
β€”
DC/AC Ratio
β€”
Ratio Check
β€”

⚠️ Continuous β‰ˆ load Γ— (1+margin); motor loads need surge headroom (LRA). DC/AC ratio 1.1–1.3 typical for grid-tie. Confirm against the inverter datasheet (continuous, peak, MPPT window). Verify before professional use.

Standards & method

✓ Independently verified 12 July 2026
Governing standard
NEC (NFPA 70) Article 690 Β· IEC 62548
Clauses applied
NEC 690.8(A) continuous output current Β· 690.7 maximum PV system voltage Β· DC/AC ratio and clipping
Core formula
DC/AC ratio = array kW_dc / inverter kW_ac (typ. 1.1–1.3) Β· output I = kWΒ·1000/(√3Β·V) three-phase
Why this matters
A DC/AC ratio above ~1.3 clips real production at midday. Below ~1.0 the inverter is oversized and runs inefficiently at part load. Also check Voc at record-low temperature against the inverter maximum.
Independently verified
12 July 2026 — Re-derived from the governing standard and checked numerically against worked reference cases from the standard itself β€” not merely tested for β€œreturns a number”.

Results are for guidance. Verify against the current edition of the governing standard and have a licensed engineer review before construction or installation.

Inverter Sizing β€” Method

The inverter must continuously supply the sum of AC loads that run together, with headroom for motor in-rush. Take the total continuous load, add a margin (β‰ˆ25%), and round up to a standard rating. For grid-tied PV the inverter is also matched to the array through the DC/AC ratio (array DC kW Γ· inverter AC kW), normally 1.1–1.3: a modest over-sizing of the array captures more energy in weak light while keeping clipping losses small.

Frequently Asked Questions

How do I size a solar inverter?

Add up the continuous AC loads, multiply by about 1.25 for surge margin, and round up to a standard inverter rating. For grid-tie also check the DC/AC ratio against the array.

What is a good DC/AC ratio?

For grid-tied PV, 1.1-1.3 is typical: the array DC kW is slightly larger than the inverter AC kW, which improves utilisation with little clipping loss.

Does the inverter need surge capacity?

Yes for motor loads (pumps, fridges, AC). Their locked-rotor/start current can be several times the running current, so the inverter peak/surge rating must cover it, not just the continuous rating.

Can the inverter be smaller than the array?

Yes - a DC/AC ratio above 1 is normal. Going much above ~1.35 starts to clip peak production; check the inverter clipping curve and any export limit.

String or microinverter?

String inverters suit unshaded arrays of similar orientation; microinverters or optimisers suit shading and multiple roof planes. Both are sized to the connected module power and the AC load.

Solar Inverter Sizing Explained

The inverter converts DC from the panels/battery into AC for loads or the grid. It is sized from two angles: the AC load it must run, and the DC array it is matched to.

Load side

Sum the continuous loads that operate together and add surge margin for motors. The continuous rating must never be exceeded; the peak rating covers brief start-up surges.

Array side

For grid-tie, the DC/AC ratio (array Γ· inverter) is typically 1.1-1.3 so the inverter runs near capacity in good sun without large clipping losses. Combine with array sizing and string sizing to confirm the MPPT voltage window.

Related: Panel Sizing, Battery Bank, PV String.